Rockwell Automation AutoMax R-Net Processor Module User Manual

Page 10

Advertising
background image

2Ć2

The resulting number indicates one of the following fault conditions:

ă1 Ć EPROM checksum error

ă2 Ć Scratchpad RAM failure

ă3 Ć Dual port memory failure

ă4 Ć Node number switch setting greater than 250

ă5 Ć Communication circuit failure

ă9 Ć Local watchdog interrupt

10 Ć Software test (negative buffer length detected)

11 Ć Software test (message length = 0 detected)

12 Ć Unused interrupt detected

13 Ć Attempt was made to access a word on an odd byte

(address error)

14 Ć System watchdog interrupt

15 Ć Bus error (RĆNet module unable to reconstruct where to

execute after unsuccessful attempt to access dual port

memory.)

RĆNET

PROCESSOR

57C429

READY
XMIT
RECV
COM OK
COM ER
COM ER
COM ER
COM ER

NODE NO.

HI

LO

C E

0

2

4

6

B

A

C E

0

2

4

6

B

A

Figure 2.1Ć AutoMax RĆNet Processor Module Faceplate

Advertising