4Ć3

4.1.1.3

Register 13 (Slot Number)
Register 13 indicates the slot location of the AutoMax RĆNet

Processor module.

4.1.1.4

Register 14 (Messages Received Count)
Register 14 indicates the number of messages received by the

AutoMax RĆNet Processor module since powerĆup. This register will

increment (up to 32767) as messages are received. This register is

reset to zero at powerĆup or can be reset by the user.

4.1.1.5

Register 15 (Receive Timeouts Count)
The AutoMax RĆNet Processor module expects to receive a response

to a message within the time period specified by register 22. If a

response is not received, a receive timeout occurs and is logged in

this register (up to 32767). This register is reset to zero at powerĆup

or can be reset by the user.

4.1.1.6

Register 16 (CRC Error Count)
CRC (Cyclic Redundancy Check) is an error detection scheme to

insure the validity of the data that is sent and received. This register

will increment (up to 32767) if a CRC error occurs. This value will

ideally remain zero. This register is reset to zero at powerĆup or can

be reset by the user.

4.1.1.7

Register 17 (Overrun Error Count)
Overrun errors are caused by receivingtoo many bits of data in a

transmission frame. (This is typically caused by missinga stop bit.)

This register will increment (up to 32767) if an overrun error occurs.

This value will ideally remain zero. This register is reset to zero at

powerĆup or can be reset by the user.

4.1.1.8

Register 18 (Illegal Message Count)
Register 18 will increment (up to 32767) each time a message frame

is received that did not contain enough bits of data. This can be

caused by transmission problems or improper protocol. This value

will ideally remain zero. This register is reset to zero at powerĆup or

can be reset by the user.

4.1.1.9

Register 19 (Messages Transmitted Count)
This register increments (up to 32767) each time a message is

transmitted from the AutoMax RĆNet Processor module. This register

resets to zero at powerĆup or can be reset by the user.

4.1.1.10

Register 20 (Lost Token Count)
This register increments (up to 32767) when no activity is detected on

the network within 10 ms.

4.1.1.11

Register 21 (Maximum Node Number)
This register defines the number of nodes on the network. At

powerĆup, the AutoMax RĆNet Processor CPU will set this location to

7 more than the node address (up to 250). For efficient operation,