Wiring Requirements

Use solid or stranded wire. All XM wiring should meet the following
specifications:

• 0.34…2.1 mm

2

(22…14 AWG) copper conductors without

pretreatment; 8.4 mm

2

(8 AWG) required for grounding the DIN rail

for electromagnetic interference (EMI) purposes

• Recommended strip length 8 mm (0.31 in.)

• Minimum insulation rating of 300V

• Soldering the conductor is forbidden

• Wire ferrules can be used with stranded conductors; copper ferrules

recommended

Grounding Requirements

Use these grounding requirements to ensure safe electrical operating
circumstances, and to help avoid potential EMI and ground noise that can
cause unfavorable operating conditions for your XM system.

DIN Rail Grounding

ATTENTION

Do not wire more than two conductors onto any single terminal.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use
zinc-plated, yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.