Input RFI Filters

9

1.

Perform the appropriate step below (A, B, C, D or E) to mount the
filter and drive.

A. 1336-RFB-7-AA, 16-AA, 30-A Filters

Mount the filter and drive to the panel. See the Dimension &
Mounting diagrams provided in this document. Drive mount-
ing information can be found in the User Manual.

B. 1336-RFB-7-A, 16-A Series B Filters

Two mounting methods are available; filter and drive (as one
assembly) or side-by-side. Choose the method that best suits
your application, then refer to the Dimension information on
page 6 and mounting diagram on page 11. Drive mounting
information can be found in the User Manual.

Important:

Hardware must be installed as shown in the
Mounting diagram on page 11.

C. 1336-RFB-30-A4, 27-B, 48-B, 80-C Filters

Using the supplied hardware, mount the filter and drive (as
one assembly) to the panel. Hardware must be installed as
shown in Figure 2 on page 11.

D. 1336-RFB-150-D, 180-D, 340-E Filters

a) Mount the drive to the panel using the Mounting diagram

provided in this document as a guide. Drive mounting
information can be found in the User Manual.

b) Using the Dimension and Mounting diagrams provided,

correctly orient and temporarily mount the filter (using
top mounting hole(s) only) to the enclosure back plane.

Important:

Filter must be carefully positioned for proper
alignment with the conduit box (and drive).

c) Insert lower filter bolt(s) and secure all hardware.

Remove the lower filter access panel and conduit box
cover.

d) Attach the conduit box to both the filter and drive using

the two nipples/fittings and locknuts provided. Refer to
the diagram on page 14 for knockout definitions and
mounting point for conduit box.

e) Route filter output leads through the conduit box and into

the drive. Replace access panel and conduit box cover.

E. 1336-RFB-475-G, 590-G, 670-G Filters

Mount the filter using the Dimension & Mounting diagrams
provided in this document. Drive mounting information can
be found in the User Manual.

!

ATTENTION: To prevent electrical shock, disconnect the
power source before installing or servicing.