Rockwell Automation 1305 RFI Filter PLUS,PLUSII,FORCE,IMPACT Installation User Manual
Page 5
Input RFI Filters
3
1. Mount the filter to the panel. Refer to the Dimension drawing
shown on the previous page.
2. Remove and discard the plastic conduit panel of the 1305.
Replace with the supplied metal conduit panel.
3. Mount the grounding bracket to the conduit panel of the drive
using the supplied hardware.
4. Using the figure below as guide, mount the drive to the filter.
Filter Mounting
5. The RFI filter must be connected between the incoming AC
supply line and the drive input terminals.
Important:
The filter may cause ground leakage currents.
Therefore a solid ground connection must be provided
as shown on the following page.
(NEMA Type 1 only) Before connecting the AC input
lines, slide the Terminal Block Cover Adapter onto the
wire. After wiring has been completed, slide the
adapter up to the filter and secure with supplied
standoffs. Place cover over adapter and secure with
supplied hardware.
!
ATTENTION: To prevent electrical shock, disconnect the
power source before installing or servicing.
Three-Phase
Input
1
Terminal Block Cover Adapter
Terminal Block Cover
JO
G
ESC
SEL
To Motor
1
Cable Supplied with Filter
1
Input power (source to filter) and output power (filter to drive and drive to
motor) wiring must be in conduit or have shielding/armor with equivalent
attenuation. Shielding/armor must be bonded to the metal conduit panel.
E
ng
lis
h