Input RFI Filters
11
Filter Mounting
Series B Filters can be mounted using either method
1
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate.
2
Refer to the Filter Selection table on page 5 for frame references and corresponding catalog numbers.
To Motor
1
Cable Supplied with Filter
1
Conduit
1
To Motor
1
Three-Phase Input
1
Access
Panel
Flat Washer
Star Washers
Bolt
Bolt
Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and in
close proximity to one another.
Important: A positive electrical bond must be
maintained between drive and filter at all 4
corners. Star washers can be eliminated
if a positive electrical bond is
assured.
Three-Phase
Input
1
Figure 1 (Side-by-Side)
1336 PLUS &
PLUS
II
Frames A1 - A3
2
Figure 2 (One Assembly)
1336 PLUS,
PLUS
II
,
FORCE & IMPACT
Frames A4, B & C
2