Rockwell Automation 1305 RFI Filter PLUS,PLUSII,FORCE,IMPACT Installation User Manual

Page 13

Advertising
background image

Input RFI Filters

11

Filter Mounting

Series B Filters can be mounted using either method

1

Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate.

2

Refer to the Filter Selection table on page 5 for frame references and corresponding catalog numbers.

To Motor

1

Cable Supplied with Filter

1

Conduit

1

To Motor

1

Three-Phase Input

1

Access

Panel

Flat Washer

Star Washers

Bolt

Bolt

Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and in
close proximity to one another.

Important: A positive electrical bond must be
maintained between drive and filter at all 4
corners. Star washers can be eliminated
if a positive electrical bond is
assured.

Three-Phase

Input

1

Figure 1 (Side-by-Side)

1336 PLUS &

PLUS

II

Frames A1 - A3

2

Figure 2 (One Assembly)

1336 PLUS,

PLUS

II

,

FORCE & IMPACT

Frames A4, B & C

2

E

ng
lis

h