Mount the module – Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 6

Advertising
background image

6

Rockwell Automation Publication ENMON-IN220D-EN-P - February 2014

XM-220 Dual Speed Module

Mount the Module

The module mounts on a XM® 941terminal base unit, catalog number 1440-TB-B. We recommend that you mount the
module after connecting the wiring on the terminal base unit. Refer to the XM-941 Terminal Base Installation Instruction,
publication

GMSI10-IN021

, or the XM-220 Dual Speed Module User Guide, publication

GMSI10-UM004

, for wiring

information.

1. Make certain the keyswitch (A) on the terminal base unit (C) is at position 4 as required for the XM-220 module.

2. Make certain the side connector (B) is pushed all the way to the le ft.

You cannot install the module unless the connector is fully extended.

3. Make sure that the pins on the bottom of the module are straight so they align properly with the connector in the

terminal base unit.

4. Position the module (D) with its alignment bar (E) aligned with the groove (F) on the terminal base unit.

5. Press firmly and evenly to seat the module in the terminal base unit.

The module is seated when the latching mechanism (G) is locked into the module.

6. Repeat the above steps to install the next module in its terminal base unit.

All grounds in the system must be tied to the same point of the same grounding electrode system.

Maintain a 2.54 cm (1 in.) minimum clearance between the module and adjacent equipment. There are no orientation
restrictions.

ATTENTION: The XM-220 module is compatible only with the XM-941 terminal base unit. Verify that the keyswitch on the
terminal base unit is at position 4 for the XM-220 module.

Do not attempt to install XM-220 modules on other terminal base units.

Do not change the position of the keyswitch a fter wiring the XM-941 terminal base unit.