Self-test – Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication ENMON-IN220D-EN-P - February 2014

XM-220 Dual Speed Module

Channel 1 and Channel 2 Indicator

Startup (Start) Indicator

Relay Indicator

Self-Test

The XM-220 module performs a self-test at powerup. The self-test includes a status indicator test and a device test. During
the status indicator test, the indicators turn on independently and in sequence for approximately 0.25 seconds.

The device test occurs a fter the status indicator test. The Module Status (MS) indicator is used to indicate the status of the
device self-test.

Color

State

Description

No color

Off

Normal operation with alarm limits on the channel.
No power applied to the module; look at Module Status indicator.

Yellow

Solid

An alert level alarm condition exists on the channel (and no transducer fault, tachometer fault or danger level alarm condition
exists).

Flashing

Tachometer fault (no transducer fault) condition exists on the channel.

Red

Solid

A danger level alarm condition exists on the channel (and no transducer fault or tachometer fault condition exists).

Flashing

A transducer fault condition exists on the channel.

Color

State

Description

Yellow

Off

Startup period is not in effect.

Solid

Startup period is in effect:
Module can inhibit the Tach Fault alarm status.
Module can monitor for locked rotor conditions.

Color

State

Description

Red

Off

On-board relay in not activated.

Solid

On-board relay is activated.

MS Indicator State

Description

Flashing red and green

Device self-test is in progress.

Solid green or flashing green

Device self-test completed successfully, and the firmware is valid and running.

Flashing red

Device self-test completed, the hardware is OK, but the firmware is invalid. Or, the firmware download is in progress.

Solid red

Unrecoverable fault, hardware failure, or Boot Loader program corruption.