Troubleshooting

21

Display

Cause

Solution

E9

Temperature limiter opened circuit (overheat).
Trips at 220F (104C).

Check connections. *
Check heat exchanger condition.*

EA

No ionization during safety time (safety time out).
Note: appliance makes 3 ignition attempts
before entering error mode “EA”.

Check gas pressure.

(see chapter

2.9

)

*

Check that gas is not diluted with air, as a
result from recent gas pipeline rework.*.
Check if vent terminal is blocked (especially
when the appliance starts up for some sec-
onds and then looses ionization signal).*
Check ionization electrode.*
Check for a proper ground.*
Check CO

2

levels.* (see chapter 9)

EC

The ionization signal momentarily disappeared
more then 5 times in less then 30 seconds. CO

2

may be out of adjustment

FA

Leakage error (gas valves do not close gas
circuit).

Check gas valve and control unit.*

F7

Ionization error (flame sensing at stand-by).

Check control unit.*

E0

Internal software/hardware failure.

Check control unit.*

A7

Hot water temperature sensor/receiver defect
(from control unit).

Check water temperature sensor/receiver and
connections.*
Check incoming water temperature to heater, it
must be above 32°F (0°C)

A9
(flashing)

Hot water temperature sensor/receiver mis-
assembled (from control unit).
Note: if display shows “A9” flashing, the
appliance can be operated normally, but
performance may be affected.

Check that the water temperature sensor/receiver is
properly assembled on the horizontal of the hot
water pipe.*
Check that the water temperature sensor/receiver is
free from corrosion or moisture.*

C1

FAN rotation too low at start-up (from control
unit).

Check supply voltage.*
Check fan and connections.*
Check control unit.*
Check if vent terminal is blocked.*

C6

FAN rotation too low at operation (from control
unit).

Check supply voltage.*
Check fan and connections.*
Check control unit.*

C7

No rotational speed sensor signal from FAN

Check fan and connections.*
Check control unit.*

CA

Water flow signal over specified maximum value

Check water valve and flow sensor.*

E2

Inlet temperature sensor fault

Check water temperature sensor/receiver and
connections.*
Check incoming water temperature to heater, it
must be above 32°F (0°C)

A2

Overheat protection fault

Check connections to the overheat protection.*
Check sensor continuity.*
Check heat exchanger sealings and walls.*

Table 5

* By installer or service technician only.