40 — ElectriCalc Pro

Wire Sizing Based
on Ambient Temperature

Find the 90°C aluminum wire size
needed to connect a 47,700 volt-amp
load to a 240 volt, single-phase source.
What is the adjusted wire size, if the
ambient temperature rating is changed
from the default 30°C to 40°C?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Set to 90°C

S 9

1 Ø 90 Cu 1 PH

Set to Al

S 4

1 Ø 90 Al 1 PH

Enter VA

47700V VA 47,700.

Enter volts

240 U

VOLT 240.

Find amps

A

AMPS 198.75

Find wire size

w

AWG 0000 AL

WIRE SIZE

Change ambient

temperature

40 S 2

AMB° 40.˚C

Find adjusted

wire size

w

AWG 250 AL

WIRE SIZE

Display Wire

w

250

209.3 AI

Amb WIRE A

Ampacity

AI WIRE A

Display NEC Table

w

NEC 310.16