Finding Voltage Drop Distance

How far from a single-phase 240-volt
source can you install a 15 amp load
using 60°C #10 aluminum branch circuit
conductors? Assume a 3% allowable
voltage drop.

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Set to aluminum

S 4

1Ø 60 Al 1 PH

Enter amps

15 A

AMPS 15.

Enter volts

240 U

VOLT 240.

Enter wire size

10 w

AWG 10 AL

WIRE SIZE

Enter 3% VD

3 v

DROP 3.0 V %

Find distance

l

FEET 123.77387

Find actual

voltage drop

v

DROP 7.2 AL V

Find % v.drop

v

DROP 3.0 AL V %

NOTE: The calculator automatically
makes adjustments for resistance using
NEC Chap 9, Table 8, if the insulation
type is other than 75°C.

* NOTE: See “Settings” for a list of
Permanent Values/settings. Changing
these settings may affect your calculations.