User’s Guide — 51

Ground Conductor Wire Size

You can use single or multiple service
entrance conductor(s) to find the
grounding electrode conductor for AC
systems. When using multiple conduc-
tors, the ElectriCalc Pro uses the
equivalent circular mils to find the
grounding electrode conductor (based
on NEC Table 250-66).

Find the grounding electrode conductor
wire size required when 2/0 is the larg-
est 3-phase 75°C copper service-
entrance conductor being used. What
is the equivalent aluminum size? What
is the equivalent circular mils?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 75º C

S 7

3Ø 75 Cu 0.

Enter wire size

00 w

AWG 00 CU

WIRE SIZE

Find ground wire

G

GRND 4 CU

size

WIRE SIZE

Find aluminum size

G

GRND 2 AL

WIRE SIZE

Find circular mils

G

CMIL 133,100.

WIRE

Display NEC Table

G

NEC 250.66

Set to 60º C

S 6 o

0.

and Clear

Advertising