Component Measured

Voltage DC to Chassis Ground

Resistance Range to cause Ground
Fault in Standby

(measured in 5K increments)

MX-MBR W/STROBE

SPKR +

SPKR -

SPKR +

SPKR -

PS CONNECTED

23.5

10

<345K - 350K

<120K - 125K

MX-MBR FIRE PHONE

PHONE +

PHONE -

PHONE +

PHONE -

CONNECTION (TB5, TB6)

21

-3

<295K - 300K

<30K - 35K

MX-MBR W/EVX-ZAB

SPKR +

SPKR -

SPKR +

SPKR -

CONNECTED

24

10

<240K - 245K

<80K - 85K

MX-MBR W/EVX-ZA

SPKR +

SPKR -

SPKR +

SPKR -

CONNECTED

24

9

<240K - 245K

<65K - 70K

MX-FPI W/MX-FPR

PHONE +

PHONE -

PHONE +

PHONE -

CONNECTED

21

-3

<205K - 210K

<20K - 25K

MX-FPI W/MX-FPO2

PHONE +

PHONE -

PHONE +

PHONE -

CONNECTED

21

-3

<205K - 210K

<20K - 25K

EVX-25(E),-50(E), -100(E)

SPKR +

SPKR -

SPKR +

SPKR -

PRIMARY AMP

24.5

10

<260K - 265K

<90K - 95K

EVX-BAB

SPKR +

SPKR -

SPKR +

SPKR -

24

10

<260K - 265K

<80K - 85K

Annunciation of “Ground Faults” on Notification Appliance Circuits

The following test points are provided to show voltage reading at terminals.

The K ohm resistance values shown annunciate a “ground fault” at panel.