Dcc ssc, Master panel controls and displays, Input card mx-ii – Harrington Signal HAVED-MP User Manual

Page 6: Master panel wiring

Advertising
background image

HMX

CONTROL

FIRE PHONE CONTROL

Alarm

Fault

Power

Paging Microphone

Message Display

System Reset

Fault Silence

Paging All-Call

Lamp Test

Function

Switches & LEDs

Fire Phone

Handset

Master Panel

Controls and Displays

PAGING/ZONE CONTROL

MP 64/P panel

P/N HS-5010 REV. C

page 6 of 12

120 VAC

TB1

TB2

TB3

TB4

TB5

P1

P2

P3

P4

J1

1
2
3

LED3

LED2

LED1

DCC

SSC

P3

LED1

P2

P1

MFP

Master Panel Wiring

NetCom Bus

FACP
EOLR

FACP

SIGNAL CKT

FACP

I/O Control

(Supervised)

(Non-Supervised)

H

N

G

(Supervised)

24V Battery

(Supervised)

+ -

(Supervised)

*1

*1

All wiring with exception of
120 VAC and Battery Connection
is Power-Limited.

Route AC power and Battery
wires to bottom-left or lower-left
side Knock-out ..

*2

*1 All Power Limited wiring must

maintain a min. 1/4“ separation
from Non Power Limited wiring.

(This requirement may be waived if
Type FPL, FPLR or FPLP wire is used
for Power Limited circuits)

*2 Wiring from FACP must be run

in conduit. Panels must be within
20’ and in the same room.

*A

*A

*A - Optional wiring for
Style 7 supervision

ASC

TB1

P4

P3

P1

P2

P5

P5

Input

Card

MX-II

TB1

TB2

PWR

refer to illustration

on page 8 for info

on jumper J1 placement

1

1

2

2

3

3

AC Power

Input

Transformer

to cabinet
backplate

2519 Fourth Avenue

Moline, IL 61265

(800) 577-5758 (v)

(309) 762-8215 (f)

www.harringtonfire.com