HMX Specifications

Communications Bus: The communications bus conforms to the RS-485 standard and requires the use of
UTP- cable for 1M Baud data rates. Wiring must be run in conduit in a daisy chain from the Master Panel to
the first Dist. Panel, from each Dist. Panel to the next Dist. Panel and from the last Dist. Panel back to the
Master Panel. When style 7 wiring is used, a separate conduit for each bus must be used.

Voltage: 5V peak-to-peak max.
Current: 50mA max.
Impedance: 120 Ohms
(max. imp. between panels)
Frequency: 1.024MHz

Power Requirements: Power supplied to the DCC module is routed to any attached peripherals. These
peripherals in turn determine whether the DCC is part of a Master Panel or a Dist. Panel.. Amplifier modules
in Dist. Panel are powered separately.

Battery Charging
Maximum charging current from EVX-25/50 is 800mA.
Maximum battery size* is 18Ah for EVX-25E and EVX-50E.
Maximum Battery size* for EVX-100E is 24 Ah.
* 12 amp hour is maximum size that will house in a MP or DP cabinet

Electrical Ratings

All circuits @ 24 VDC

MASTER PANEL

Stand by condition

Alarm condition

DCC

73mA

*147mA combine DCC, ASC & MMC

ASC

34mA

MMC

38mA

MFP

10mA

20mA

MFH

12mA

12mA

IOI

19mA

30mA

SSC

29mA

15mA

SLC

0.2mA

8mA

TOTAL

215.2

232mA

DISTRIBUTED PANEL

Stand by condition

Alarm condition

DCC

76mA

*104mA combine both DCC and MBR

MBR

28mA

AMI

16mA

26mA

FPI

20mA

41mA

MBK

6mA

42mA

TOTAL

149mA

213mA

P/N HS-5010 REV. C

page 12 of 12