Input card mx-ii, Tb1 tb2 – Harrington Signal HAVED-MP User Manual

Page 9

Advertising
background image

MX-II / PWR

Connection Detail

Terminal Designation

Wiring
FACP Bell Circuit - #18 AWG.
Input Control - #24 AWG.
(Must be in the same room within
20 feet of panel, in conduit)

IOI

1- 8 Input Control
(1mA 5VDC)
9 Circuit Common (NEG)
10 FACP Bell Circuit + (Alarm
11 FACP Bell Circuit - Polarity)

(10mA 24VDC)

MX-PWR

TB2

1 FACP EOLR
2 FACP EOLR
3 Circuit Common (NEG)
4-11 Input Control

(1mA 5VDC)

TB1

PWR

Input

Card

MX-II

TB1

TB2

To FACP Input Control

To FACP Bell Circuit

(24V 10mA min. rating)

Common

NEG

+

1

2
.
.
.

7

-

(N.O. Dry Contact)

8

End of Line Resistor
for FACP Bell Circuit

1

11

11

1

DCC

TB3

2 3 4

(Factory wired)

This wiring is Supervised by the FACP and

is Power Limited PROVIDED the FACP Bell

Circuit is Power Limited.

Non-Supervised - Power Limited

Supervised

Power Limited

In normal operation, FACP
will supervise system by
reading its EOLR. Under any
Fault condition in the HMX
system a contact will open
resulting in a Fault on the
FACP bell circuit.

**ALARM Polarity shown**

1

1

2

2

3

3

jumper J1
remove before connecting batteries

P/N HS-5010 REV. C

page 9 of 12

TB1:

Ter. 1 & 2
battery connections
1- circuit negative
2-+24VDC

max charging current: 1A
max reccomended battery
size: 18ah

TS1:

Ter. 1,2,3
+24 VDC output
1-fault report output
2-+24 VDC
3-circuit negative

TS2:

Ter. 1,2,3
28
VAC input
1,2 - 28 VAC in
3 - ground fault detect,
to chassis

(optional- if

unit mounted with snap
track, connection is necessary.
If metal standoff used in lower
left corner, connection is not
necessary)

TS-1

TS-2

2519 Fourth Avenue

Moline, IL 61265

(800) 577-5758 (v)

(309) 762-8215 (f)

www.harringtonfire.com