Warning, Ктм ъ·´¬»® я®®¿²¹»³»²¬ ктл я·® ь – Klimaire GM80S Series User Manual

Page 14

Advertising
background image

ïî

I&O manual

WARNING

Failure to follow this warning could result in personal injury, or
death.
Never operate a furnace without a filter or with filter access door
removed.

CARBON MONOXIDE AND POISONING HAZARD

ктм Ъ·´¬»® Я®®¿²¹»³»²¬

ктл Я·® Ь«½¬-

General Requirements

The duct system should be designed and sized according to accepted
national standards such as those published by: Air Conditioning
Contractors Association (ACCA), Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) or American Society of
Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or
consult The Air Systems Design Guidelines reference tables available
from your local distributor. The duct system should be sized to handle
the required system design CFM at the design external static
pressure. The furnace airflow rates are provided in Table 6-AIR
DELIVERY -CFM (Without Filter).
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply and return-duct connections to furnace with code
approved tape or duct sealer.

NOTE: Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated and sealed to
enhance system performance. When air conditioning is used, a
vapor barrier is recommended.
Maintain a I-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36 in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further
requirements.

Ductwork Acoustical Treatment

NOTE: Metal duct systems that do not have a 90 degree elbow and
10 ft. (3 M) of main duct to the first branch take-off may require
internal acoustical lining. As an alternative, fibrous ductwork may be
used if constructed and installed in accordance with the latest edition
of SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA 90B
as tested by UL Standard 181 for Class 1 Rigid air ducts.

Supply Air Connections

For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the
airstream. The cover attachment shall prevent leaks.

Upflow and Horizontal Furnaces

Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90° with wide duct pliers. The supply-air duct must
be connected to ONLY the furnace supply-outlet-air duct flanges or
air conditioning coil casing (when used). DO NOT cut main furnace
casing side to attach supply air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external to
furnace main casing.
NOTE: For horizontal applications, the top-most flange may be bent
past 90 degrees to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the coil
are performed.

Downflow Furnaces

Connect supply-air duct to supply-air outlet on furnace. Bend flange
inward past 90° with wide duct pliers. The supply-air duct must be
connected to ONLY the furnace supplyoutlet or air conditioning coil
casing (when used). When installed on combustible material,
supply-air duct must be connected to ONLY the accessory subbase
or a factory approved air conditioning coil casing. DO NOT cut main
furnace casing to attach supply side air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external to
furnace casing.

FILTER TYPE

Air velocity through throwaway filters may not exceed 300 feet per
minute (91.4m/min). All velocities over this require the use of hight
velocity filters. If a normal speed desposable filter is used and air
speed exceeds 300 feet per minute(FPM), two side returns or one
side return and the bottom return may be needed. For airflow, refer to
Table 3.

If disposable filters are used air throw away passage through filters
should be increased to twice the size of original air opening by using
a transition duct or using two filters in V shap in normal duct size.

Locate the 4 cutout locations. These indicate the size of the cut-out
to be made in the furnace side panel. Refer to Fig 19, "Side Return
Cutout Markings".

Install the side filter rack followi ng the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.
IMPORTANT: Some accessories such as electronic air cleaners and
pleated media may require a larger side opening. Follow the instruc-
tions supplied with that accessory for side opening requirements.

Fig. 19

Side Return Cutout Markings

Front of
Furnace

Corner
Markings

Downflow Filters

Downflow furnaces typically are inst alled with the filters located above
the furnace, extending into the re turn air plenum or duct. Any branch
duct (rectangular or round duct) attached to the plenum must attach to
the vertical plenum above the filter height.
Filter(s) may be located in the duct system external to the furnace using
an external duct filter box attached to the furnace plenum or at the end
of the duct in a return filter grille(s). The use of straps and/or supports is
required to support the weight of the external filter box.

SIDE RETURN

One of the most common causes of a problem in furnace is a blocked
or dirty filter. The filter must be inspected monthy for dirt accumulation
and replace it if neccessarily.

FILTER SIZE
See

recommended filter size and type in Table 4.

Advertising