REPAIR & REPLACEMENT

1. After repairing any component:

a. check that electrical connections are correct and secure (see Figure 9),

b. remove any foreign material from enclosures,

c. install and secure all covers,

d. ensure that all fasteners are tight,

e. remove all foreign objects from heater, and

f. ensure air exits through louvers and fan rotates counterclockwise when

viewed from rear of heater (see Figure 14).

C O R E

The heater core is vacuum charged and not field repairable.

For core removal:

1. Remove cabinet bottom and element enclosure cover.

2. Disconnect all wires entering element enclosure (see Figure 10).

3. Slightly loosen all cabinet bolts shown in Figure 10, to prevent the core

from binding.

4. With an assistant supporting the weight of the core, remove the 3 core

mounting bolts. Carefully lower the core out of the cabinet

(see Figure 11).

5. To return core to factory, use crate supplied with exchange core

to protect

the element terminals and plate threads.

6. To reinstall, lift the core up into cabinet while an assistant guides the

element wires into the element enclosure conduit.

7. Position the core and tighten the 3 core mounting bolts. Tighten the

remaining cabinet bolts.

T E M P E R AT U R E H I G H - L I M I T

1. Remove temperature high-limit assembly and clean the inside of the

thermowell (see Figure 12). A clean thermowell will ensure good

thermal contact.

2. Use only a factory supplied temperature high-limit to ensure safe operation.

(refer to the instructions that accompany the replacement Temperature High-

Limit Kit).

3. Reinstall the temperature high-limit assembly with the snap ring and spring

into the thermowell without damaging the insulating tube. Secure in place

with the cotter pin (see Figure 13).

MOTOR, FAN & FAN GUARD

1. Remove bolts holding the motor to the motor mount. On units with a built

in thermostat, remove the bolts on the back of the thermostat enclosure.

2. Remove conduit #1 located between motor junction box and control

enclosure by turning it in the direction illustrated (see Figure 14).

Note conduits #1 and #2 are not interchangeable and have left hand threads on

one end, this end is indicated by a machined groove.

3. Remove the 2 piece fan guard assembly (see Figure 15).

4. Lift the motor assembly off the motor mount.

5. Before removing the fan, measure and record the location of the fan hub on the

motor shaft (see Figure 16). If difficult to remove, use a gear puller on the fan hub.

6. To reassemble, place motor assembly onto motor mount and fasten the fan guard

to cabinet.

7. Simultaneously engage and tighten both ends of conduit #1 into enclosures.

Leave a 1/16” to 3/16” (1.6 to 4.8 mm) gap between the motor and fan guard

(see Figure 16). Adjust conduit #2 to center the fan in the shroud.

8. To ensure a minimum 5 thread engagement, threaded ends of conduits must

protrude a minimum of 1/16” (1.6mm) into enclosures. The groove on conduit #2

must not be more than 7/8” (22mm) from motor coupling (see Figure 14).

9. Bolt motor to motor mount. Manually spin the fan blade to ensure fan rotates freely.

10. Air must exit through louvers and fan must rotate counterclockwise when viewed

from rear of heater (see Figure 14).

FIGURE 14

FIGURE 12

FIGURE 10

}

Loosen

bolts

only,

do not

remove.

Loosen

bolts

only,

do not

remove.

Element

Enclosure

Remove this

core mounting

b o l t & t w o

others on the

opposite side.

Rotation

Air inlet

Conduit #2

Conduit #1

Remove

Install

7/8” (22mm)
(From groove to
face of coupling)

Thermowell

Control

Enclosure

Conduit

Junction

Enclosure

WARNING

Disconnect heater from power supply at integral disconnect or fuse box before

opening enclosures or servicing heater. Lock the switch in the “OFF” (open)

position and/or tag the switch to prevent unexpected power application.

IF INTEGRAL DISCONNECT IS BEING SERVICED, verify that power has

been disconnected at fuse box or main panel. Lock the switch in the “OFF”

(open) position and/or tag the switch to prevent unexpected power application.

Heater surfaces may be hot.

Remove

Install

3/32”

(2mm)

Drop

FIGURE 13

FIGURE 11