Rear View of Heater

FIGURE 8

FIGURE 7A

FIGURE 6

Fan

rotation

1“ NPT opening
for field wiring

Air
intake

Motor
junction box

Optional factory

installed built-in

room thermostat.

Optional factory

installed built-in

disconnect.

Connect supply conductors
to this side of contactor.

For a 1-phase
heater, use these
contactor lugs.

Contactor load
side terminals, this
side for factory
wiring only.

Active and spare
fuses (see parts list)

Printed circuit board’s
terminal block

Control enclosure
and cover

Do not install conduit below heater (see Figure 3).

Control Enclosure & Field Wiring

Air exits through
louvers.

3. Heater may be supplied with a factory installed built-in integral
disconnect. (See Figure 7B)
Field Wiring for Integral Disconnect:

a. Power Supply conductors and Ground conductor pass through

1"NPT opening of Disconnect Enclosure (see Figure 7B).

Supply conductors to be wired to Disconnect Switch inside.

Ground conductor to be wired to Ground Lug fastened to inside

of Disconnect Enclosure.

b. If applicable, Remote Room Thermostat conductors pass

through 3/4"NPT opening (see Figure 7b) and are to be wired to

printed circuit board terminals marked “T’STAT”.

c. To reduce risk of ignition of hazardous atmospheres, conduit

runs must have a sealing fitting connected within 18 inches

(457 mm).
Factory installed conduits require no further sealing. Integral

Disconnect is sealed at factory.

4. The internal grounding terminal in the control enclosure (or in the

integral disconnect enclosure when this option is provided) shall

be used as the equipment grounding means. An external bonding

terminal is provided for a supplementary bonding connection where

local authorities permit or require such a connection.

Sealed at Factory

Switch load side
terminals, this
side for factory wiring
only.

1" NPT
(Power Supply)

3/4" NPT

(Remote Room

Thermostat

if applicable)

Terminals marked

“T’STAT”

Connect Supply Conductors to
this side of Switch

For a 1-phase heater use these
Switch terminals

FIGURE 7B

Optional Built-in Disconnect

& Field Wiring

F I N A L I N S P E C T I O N

1. Before application of electrical power:

a. Check that all connections are secured and comply with the

applicable wiring diagram (see Figure 9) and code requirements,

b. Confirm that the power supply is compatible with the data plate

rating of the heater,

c. Remove any foreign objects from the heater,

d. Install all covers and verify that all enclosures are well secured, and

e. Ensure that the fan rotates freely. See Figure 6 for proper direction

of fan rotation.