9

F X 5 T E C H N I C A L D ATA F O R 5 0 H Z

E L E C T R I C H E AT E R S

C US

Model

Note

Air Flow

V

oltage

Nominal

W

attage

Phase

Max. Motor Nameplate

Current

Heater W

attage

Total

Current

Minimum Circuit Ampacity

Supply W

ire

Maximum Fuse Size

Temperature

Rise

Core Kit

Part Number

Contactor

Part

Number

(CFM) (V) (kW)

(W)

(A)

(A)

(AWG)

(A)

°F

°C

FX5-220150-025

400

220

2.5

1

2.7

2270

11.4

14.3

14

15

19.8

11.0 12122

3618

FX5-220150-042

400

220

4.2

1

2.7

3950

19.1

23.9

10

25

33.2

18.4 12123

3618

FX5-220150-063

700

220

6.3

1

2.7

6050

28.6

35.8

8

40

28.5

15.8 12124

3618

FX5-220150-084

700

220

8.4

1

2.7

8140

38.2

47.8

6

50

37.9

21.1 12125

3619

FX5-220150-126

* 1450 220 12.6 1

1.4

12100 57.3

71.6

2

75

27.5

15.3 12126

3619

FX5-230150-028

400

230

2.8

1

2.7

2480

12.2

15.3

12

20

22.1

12.3 12122

3618

FX5-230150-046

400

230

4.6

1

2.7

4310

20.0

25.0

10

25

36.4

20.2 12123

3618

FX5-230150-069

700

230

6.9

1

2.7

6610

30.0

37.5

8

40

31.2

17.3 12124

3618

FX5-230150-138

* 1450 230 13.8 1

1.4

13200 59.9

74.9

2

80

30.1

16.7 12126

3619

FX5-380350-025

400

380

2.5

3

0.7

2270

3.8

4.8

16

5

19.8

11.0 12122

3618

FX5-380350-042

400

380

4.2

3

0.7

3950

6.4

8.0

16

10

33.2

18.4 12123

3618

FX5-380350-063

700

380

6.3

3

0.7

6050

9.6

12.0

14

15

28.5

15.8 12124

3618

FX5-380350-084

700

380

8.4

3

0.7

8140

12.8

16.0

12

20

37.9

21.1 12125

3618

FX5-380350-125

1450 380 12.5 3

0.7

12100 19.0

23.8

10

25

27.3

15.1 12126

3618

FX5-380350-209

3000 380 20.9 3

1.0

20300 31.8

39.8

8

40

22.0

12.2 12128

3618

FX5-400350-028

400

400

2.8

3

0.7

2480

4.0

5.0

16

5

22.1

12.3 12122

3618

FX5-400350-046

400

400

4.6

3

0.7

4310

6.6

8.3

16

10

36.4

20.2 12123

3618

FX5-400350-069

700

400

6.9

3

0.7

6610

10.0

12.5

14

15

31.2

17.3 12124

3618

FX5-400350-093

700

400

9.3

3

0.7

8900

13.4

16.8

12

20

42.0

23.3 12125

3618

FX5-400350-139

1450 400 13.9 3

0.7

13200 20.1

25.1

10

30

30.3

16.8 12126

3618

FX5-400350-185

1450 400 18.5 3

0.7

17800 26.7

33.4

8

35

40.3

22.4 12127

3618

FX5-400350-231

3000 400 23.1 3

1.0

22200 33.3

41.6

8

45

24.3

13.5 12128

3619

FX5-415350-037

400

415

3.7

3

0.7

3510

5.1

6.4

16

10

29.3

16.3 12130

3618

FX5-415350-075

700

415

7.5

3

0.7

7240

10.4

13.0

14

15

33.9

18.8 12132

3618

FX5-415350-149

1450 415 14.9 3

0.7

14500 20.7

25.9

10

30

32.5

18.1 12134

3618

FX5-415350-224

3000 415 22.4 3

1.0

21800 31.2

39.0

8

40

23.6

13.1 12136

3618

FX5-440350-042

400

440

4.2

3

0.7

3950

5.5

6.9

16

10

33.2

18.4 12130

3618

FX5-440350-084

700

440

8.4

3

0.7

8140

11.0

13.8

14

15

37.9

21.1 12132

3618

FX5-440350-168

1450 440 16.8 3

0.7

16300 27.5

34.4

8

35

36.6

20.4 12134

3618

FX5-440350-210

3000 440 21.0 3

1.0

20300 27.5

34.4

8

35

22.1

12.3 12135

3618

NOTES:

* Exceeds the 48 Amp Circuit Limit of NEC 424-22. DS5 not available for these units.

1. Minimum conductor size for 86˚F (30˚C) ambient. Derate conductor for ambient temperature. Use minimum 194˚F (90˚C) insulation.

2. Heater is functioning normally if at rated voltage the amp draw is within 10% of the value in this table.

3. Operation at lower voltages will result in reduced heat output and amp draw

4. Add "T" to model number when adding a built-in thermostat

5. Add "D" to model number when adding a built-in disconnect switch

6. Add "P" to model number when adding a built-in pilot light

7. Add "S" to model number when adding a 3-way switch

8. Add "H" to model number for units with high "off" (deenergized) ambient temperatures

9. Add "U" to model number for units with continuous fan option.

10. Add "A" to model number for units with stainless steel cabinet.