CCI Thermal Technologies FX5-SD - Explosion-Proof Electric Air Unit Heater User Manual

Page 10

Advertising
background image

10

F x 5 - s d t e c h n i c a l d ata F o r 6 0 h z

e l e c t r i c h e at e r s

C US

model

n

ote

v

oltage

n

ominal

W

attage

phase

m

ax.

m

otor

n

ameplate c

urrent

h

eater

W

attage

total

c

urrent

m

inimum circuit

a

mpacity

supply W

ire

m

aximum

Fuse

size

temperature

rise

c

ontactor

part

n

umber

(v) (kW)

(W)

(a)

(a)

(aWg)

(a)

°c

°F

FX5-SD-208160-030

208

3.0

1

2.7

2700

14.4

18.0

12

20

10.5

19.0

3619

FX5-SD-208160-050

208

5.0

1

2.7

4700

24.0

30.0

10

30

17.6

31.6

3619

FX5-SD-208160-075

208

7.5

1

2.7

7200

36.1

45.1

6

50

15.5

27.9

3619

FX5-SD-208160-100 * 208 10.0 1

2.7

9690

48.1

60.1

4

70

20.7

37.2

3619

FX5-SD-208360-030

208

3.0

3

1.4

2700

8.3

10.4

14

15

6.2

11.2

3619

FX5-SD-208360-050

208

5.0

3

1.4

4700

13.9

17.4

12

20

10.3

18.6

3619

FX5-SD-208360-075

208

7.5

3

1.4

7200

20.8

26.0

10

30

15.5

27.9

3619

FX5-SD-208360-100

208 10.0 3

1.4

9700

27.8

34.8

8

35

20.7

37.2

3619

FX5-SD-208360-150

208

15

3

1.4

14400 41.6

52.0

6

60

15.1

27.1

3619

FX5-SD-240160-030

240

3.0

1

2.7

2700

12.5

15.6

12

20

10.5

19.0

3619

FX5-SD-240160-050

240

5.0

1

2.7

4700

20.8

26.0

10

30

17.6

31.6

3619

FX5-SD-240160-075

240

7.5

1

2.7

7200

31.3

39.1

8

40

15.5

27.9

3619

FX5-SD-240160-100

240 10.0 1

2.7

9700

41.7

52.1

6

60

20.7

37.2

3619

FX5-SD-240160-150 * 240 15.0 1

1.4

14400 62.5

78.1

2

80

15.1

27.1

3619

FX5-SD-240360-030

240

3.0

3

1.4

2700

7.2

9.0

14

15

10.5

19.0

3619

FX5-SD-240360-050

240

5.0

3

1.4

4700

12.0

15.0

14

15

17.6

31.6

3619

FX5-SD-240360-075

240

7.5

3

1.4

7200

18.0

22.5

10

25

15.5

27.9

3619

FX5-SD-240360-100

240 10.0 3

1.4

9700

24.1

30.1

8

35

20.7

37.2

3619

FX5-SD-240360-150

240 15.0 3

1.4

14400 36.1

45.1

6

50

15.1

27.1

3619

FX5-SD-480160-030 ° 480

3.0

1

1.3

270

6.3

7.9

14

15

10.58 19.0

3619

FX5-SD-480160-050 ° 480

5.0

1

1.3

4700

10.4

13.0

14

15

17.6

31.6

3619

FX5-SD-480160-075 ° 480

7.5

1

1.3

7200

15.6

19.5

12

20

15.5

27.9

3619

FX5-SD-480160-100 ° 480 10.0 1

1.3

9100

20.8

26.0

10

30

20.7

37.2

3619

FX5-SD-480160-150 ° 480 15.0 1

1.3

14400 31.3

39.1

8

40

15.1

27.1

3619

FX5-SD-480160-200 ° 480 20.0 1

1.3

19400 41.7

52.1

6

60

20.1

36.1

3619

FX5-SD-480360-030

480

3.0

3

0.7

2700

3.6

4.5

14

15

10.5

19.0

3619

FX5-SD-480360-050

480

5.0

3

0.7

4700

6.0

7.5

14

15

17.6

31.6

3619

FX5-SD-480360-075

480

7.5

3

0.7

7200

9.0

11.3

14

15

15.5

27.9

3619

FX5-SD-480360-100

480 10.0 3

0.7

9700

12.0

15.0

14

15

20.7

37.2

3619

FX5-SD-480360-150

480 15.0 3

0.7

14400 18.0

22.5

10

25

15.1

27.1

3619

FX5-SD-480360-200

480 20.0 3

0.7

19400 24.1

30.1

8

35

20.1

36.1

3619

FX5-SD-480360-250

480 25.0 3

1.0

24200 30.1

37.6

8

40

12.2

22.0

3619

FX5-SD-480360-300

480 30.0 3

1.0

29200 36.1

45.1

6

50

14.6

26.4

3619

FX5-SD-480360-350

480 35.0 3

1.0

34200 42.1

52.6

6

60

17.1

30.7

3619

FX5-SD-600360-030

600

3.0

3

0.6

2700

2.9

3.6

14

15

10.5

19.0

3619

FX5-SD-600360-050

600

5.0

3

0.6

4700

4.8

6.0

14

15

17.6

31.6

3619

FX5-SD-600360-075

600

7.5

3

0.6

7200

7.2

9.0

14

15

15.5

27.9

3619

FX5-SD-600360-100

600 10.0 3

0.6

9700

9.6

12.0

14

15

20.7

18.1

3619

FX5-SD-600360-150

600 15.0 3

0.6

14400 14.4

18.0

12

20

15.1

27.1

3619

FX5-SD-600360-200

600 20.0 3

0.6

19400 19.2

24.0

10

25

20.1

36.1

3619

FX5-SD-600360-250

600 25.0 3

0.8

24200 24.1

30.1

8

35

25.1

45.2

3619

FX5-SD-600360-300

600 30.0 3

0.8

29200 28.9

36.1

8

40

14.6

26.4

3619

FX5-SD-600360-350

600 35.0 3

0.8

34200 33.7

42.1

8

45

17.1

30.7

3619

notes:

* Exceeds the 48 Amp Curcuit limit of NEC 424-22. DS5 not available for these units.

1. Minimum conductor size for 30˚C (86˚F) ambient. Derate conductor for ambient temperature. Use minimum 90˚C (194˚F) insulation.

2. Heater is functioning normally if at rated voltage the amp draw is within 10% of the value in this table.

3. Operation at lower voltages will result in reduced heat output and amp draw

4. Add "T" to model number when adding a built-in thermostat

5. Add "D" to model number when adding a built-in disconnect switch

6. Add "U" to model number for units with continuous fan option.

7. Add "A" to model number for units with stainless steel cabinet.

Advertising