CCI Thermal Technologies FX5-SD - Explosion-Proof Electric Air Unit Heater User Manual

Page 11

Advertising
background image

11

Nominal kW

2.5 3.7 & 4.6 6.3 & 7.5

8.4

12.5 & 12.6 14.9 & 16.7

20.9

22.4

Max. Altitude

(ft.)

12,000

8,000

10,000

7,000

10,000

7,000

10,000

7,000

(m)

3,658

2,438

3,048

2,134

3,048

2,134

3,048

2,134

Air Flow @ 21°C (m3/hr.)

679

1189

2463

5096

@ 70°F (CFM)

400

700

1450

3000

Horizontal Air Throw (ft.)

13

25

35

60

(m)

4.0

7.6

10.7

18.2

Max. Mounting Height (ft.)

7

10

10

20

(to underside)

(m)

2.1

3.0

3.0

6.1

Motor Power

(HP)

1/2

1/2

1/2

(min)

(kW)

0.373

0.373

0.373

Fan Diameter

(in.)

12

16

20

(mm)

305

406

508

Net without

(lbs.)

140

168

201

Weight DS5

(kg)

63.5

76.2

91.2

with

(lbs.)

152

180

213

DS5

(kg)

78.9

91.6

96.6

Shipping without

(lbs.)

194

218

252

Weight DS5

(kg)

88

98.9

114.3

with

(lbs.)

206

230

264

DS5

(kg)

93.4

104.3

119.7

Hazardous Location Rating

Class I, Groups C and D; Class II, Groups E, F and G;

Temperature Code T3B [165C (329F)]

Enclosures

NEMA Type 7 & 9. For dry, indoor use only. Do not immerse in water. Do not store or use

in areas exposed to rain or snow

Motor Type

Explosion-proof. Thermally protected TEFC Arctic Duty. Permanently lubricated ball

bearings.1425 RPM. Comes with mobil grease for low temperature operation.

Fan

Aluminum blade. Steel spider and hub with 5/8 in. (15.875 mm) bore.

Fan Guard

Split design with close wire spacing. 1/4 in. (6.3 mm) dia. probe will not enter

Mounting Holes

Four 9/16 in. (14.3 mm) diameter holes at top of heater

Heating Elements

Three long-life, low watt-density, high grade metal-sheathed elements

Primary automatic reset type, snap-action bimetal, open on temperature rise.

Temperature High-Limit

Rated 100,000 cycles at 15 amp, handles 0.128 amps/Secondary automatic reset type,

snap-action bimetal, close on temperature rise. Rated 100,000 cycles at 15 amp, handles

0.128 amps

Breaker Switch

Manual reset, thermal-magnetic trip unit. Provides short-circuit protection and thermal

protection.
Control Circuit

120 Volts, 0.128 amps, 15VA. (Grounded)

Optional Built-in Thermostat

Explosion-proof. 2°C to 28°C (36°F to 82°F)

Optional Built-in Disconnect Switch

DS5 for use only on heaters with total current not exceeding 48-Amps

Lockout handle accepts 1/4” diameter padlock shackle

Control Transformer

Multi-tap primary, 120 V secondary, 50 VA

Contactor

75 amps. Rated for 500,000 mechanical operations. 120 Volts, 15VA coil

(separately fuse-protected)

Heat Transfer Fluid

Long life formulated propylene glycol and water

Cabinet Material

14 ga. (0.075 in.) (1.90 mm) steel. Epoxy coated with five-stage pretreatment, including

iron phosphate. Optional stainless steel

Core

Steel with integral aluminum fins, vacuum charged and hermetically sealed

Conduit Material

Heavy walled, 0.122 in. (3.1 mm) steel

Overpressure Protection

Preset 100 psig (690 kPa) pressure relief valve, aluminum body, no field serviceable parts

Operational Temperature Limitations

-20°C to 40°C (-4°F to 104°F)

Storage Limitations

-45°C to 80°C (-49°F to 176°F), short term to 120°C (248°F). Do not immerse in water

Do not expose to rain or snow.

s p e c i F i c at i o n s F o r a l l 5 0 h z m o d e l

Advertising