Preventative maintenance grid, Warning – CCI Thermal Technologies FX5-SD - Explosion-Proof Electric Air Unit Heater User Manual

Page 2

Advertising
background image

2

For Electric Forced Air Heaters

Heater Model: _________________________ Serial No.: ___________________________
Date of Maintenance: ___________________ Maintenance Done By: _________________
Comments: _________________________________________________________________
__________________________________________________________________________

WARNING

Disconnect heater from power supply at integral disconnect or fuse box before opening enclosures or servicing heater.

Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.

IF INTEGRAL DISCONNECT IS BEING SERVICED, verify that power has been disconnected at fuse box or main panel.

Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.

This heater should only be serviced by personnel with heating and hazardous location equipment experience.

Photocopy

this page

for reuse.

Preventative Maintenance Grid

Regular Service

Severe Service

Annual

Start Up

1 Month

3 Month

12

Month

Annual

Start Up

1 Month

3 Month

12

Month

Clean:

ƒ

Finned Tubes

ƒ

Fan

ƒ

Fan Guard

ƒ

Motor

ƒ

Louvers

Remove dust using compressed air.

Do not Spray with water or

solvents.

Do not immerse in water or

solvents.

X

X

X

Electrical

Check all terminal

connections and

conductors.

Tighten loose connections.

Replace conductors with damaged

insulation & frayed wiring. For

drilling rigs, this should be done

with every rig re-location.

X X X X

Inspect contactor

contacts.

If badly pitted, burned or welded

shut, replace with factory supplied

contactor. For drilling rigs, this

should be done with every rig re-

location.

X X X

Check Fuses

The Correct fuse rating and type

are printed on the circuit board.

Always ensure a backup fuse is

available on the PCB. For drilling

rigs, this should be done with

every rig re-location.

X X

Mechanical

Check for fluid

leakage

Inspect the Pressure Release Valve

label indicator for signs of rupture

and degradation. If any fluid

leakage occurs from the heater,

disconnect it from the power

supply and have the core replaced

immediately. For drilling rigs,

this should be done with every

rig re-location.

X X X

Check all enclosures The interiors of each enclosure

must be clean, dry and free of

foreign materials. For drilling

rigs, this should be done with

every rig re-location.

X X X

Check motor shaft

bearing play

If the motor does not run quietly

and smoothly and has excessive

play replace the motor. For

drilling rigs, this should be done

with every rig re-location.

X X X

h e at e r m a i n t e n a n c e c h e c k l i s t

p r e v e n tat i v e m a i n t e n a n c e g r i d