Introduction

The Amico Automatic Gas Manifold is a one of its kind designed to provide a reliable, uninterrupted supply of gas to
a hospital or other medical facility. The manifold utilizes multiple high-pressure cylinders divided into two equal banks.
One bank is designated as a “Primary” source of gas while other the bank stands in reserve as a “Secondary” source.

A display of LED’s on the front of the manifold indicates the status of the gas supply. Each bank has a green (IN USE),
yellow (READY) and red (EMPTY) LED. When the primary bank of cylinders is depleted, the manifold will automatically
switch to the secondary bank of cylinders without interruption of gas fl ow to the facility. The red LED will illuminate
when a bank is depleted and two normally closed dry contacts for the reserve In-use alarm will open. One or both sets
of contacts may be wired to an external alarm, remote buzzer and or a building management system.

When replacement cylinders are attached to the depleted bank, the red LED goes out and the yellow LED illuminates
indicating that the bank has been automatically designated as the secondary supply. No other user interaction is
required. Both sets of dry contacts close to cancel any external alarm condition.

The power supply is connected to the top right hand corner of the manifold. Connections from the manifold to Amico
master alarm must be made from terminals marked C/Signal, to the appropriate terminals (Reserve In-use) on the mas-
ter Alarm or a remote buzzer.

The enclosure for the manifold is NEMA-1 (general purpose applications only) and it is not recommended to be mounted
outdoors.

The manifold has a removable front cabinet. The pre-assembled circuit board is mounted directly to the back plate of
the manifold. This design will reduce installation time and eliminate the risk of improper installation, since each of the
components of the manifold are connected and tested at the factory.

The Amico Automatic Gas Manifold is designed in accordance with the National Fire Protection Association (NFPA 99)

FEATURES INCLUDE:

Input power to the manifold is 110- 240 VAC, 50-60Hz

Incorporates six LED’s display - readable in poor lighting conditions

Dual line Pressure regulators.


Single vent access from line & operating relief valve

Wall mounting bracket attached to manifold for easy installation


Manifold complies with NFPA 99