N 142, Example 2: start a specific motor – Baumer N 142 User Manual

Page 10

Advertising
background image

N 142

www.baumer.com

10

Example 1: Readout current status (Status = 0 = not released)

SOH Adr Cmd EOT CRC

Transmission

01h 20h 44h 04h 04h

SOH Adr Cmd Stat. EOT CRC

Response

01h 20h 44h 30h 04h 64h

Example 2: Start a specific motor

SOH Adr Cmd Stat. EOT CRC

Transmission

01h 20h 44h 31h 04h 66h

SOH Adr Cmd Stat. EOT CRC

Response

01h 20h 44h 31h 04h 66h


Example 3: Start all motors by broadcast command (identifier = 99)

SOH Adr Cmd Stat. EOT CRC

Transmission

01h 83h 44h 31h 04h 7Bh

Response

Not confirmed


Motor holding torque off / on, command „DB“ (44h, 42h)

Prior to utilizing the “DB” command to disable / enable the holding torque it must be activated first in command
„m“ since otherwise command „DB“ remains ineffective.
Holding torque always enable means that only motive shaft positioning operations are possible - either by aid of
the two keys provided or by a corresponding command via interface. The holding torque is automatically
disabled as soon as the motor is getting a start command and will later automatically be re-enabled. Manual
positioning operations by hand cranks etc require disabling the holding torque first by command “DB”.

Following modes are available:

Status

Function

0 (30h) holding torque disable
1 (31h) holding torque enable


Example 1: Read out current status (status = 0 : without holding torque)

SOH Adr Cmd

SCmd

EOT CRC

transmitted

01h 20h 44h 42h 04h 80h

SOH Adr Cmd

SCmd

Stat. EOT CRC

response

01h 20h 44h 42h 30h 04h 6Dh


Example 2: Disable holding torque (status = 0 : unblock holding torque)

SOH Adr Cmd

SCmd

Stat. EOT CRC

transmitted

01h 20h 44h 42h 30h 04h 6Dh

SOH Adr Cmd

SCmd

Stat. EOT CRC

response

01h 20h 44h 42h 30h 04h 6Dh


Example 3: Disable holding torque for all motors by broadcast-command (ID=99)

SOH Adr Cmd

SCmd

Stat. EOT CRC

transmitted

01h 83h 44h 42h 30h 04h

57h

response

not confirmed


Note: If the holding torque is enabled (command „m“), clamping will always be activated upon power on, reason
why holding torque OFF by command „DB0“ remains only effective whilst device is under power supply.