4.5. Specific commands

Command

code

Data amount

in bytes

read

write

Broad-

cast

Save in

EEPROM

Significance

K (4Bh)

-

-

X

X

X

Specific command: Profile reset (delete)

Q (51h)

1

-

X

X

X

Specific command: N 142 reset

X (58h)

2 / 4 / 8

X

-

-

-

Specific command: Read device data


4.5.1. SPA profile reset, command „K“ (4Bh)

This command is clearing all previously programmed profiles.

Example 1: Profile reset of a specific N 142

SOH Adr Cmd Data EOT CRC

Transmission

01h 20h 4Bh 7Fh 04h C6h

SOH Adr Data EOT CRC

Response

01h 20h 6Fh 04h 52h N 142 replies by standard response ‚o’ (6Fh) = OK



Example 2: General profile reset in all SPAs by broadcast command (identifier = 99)

SOH Adr Cmd Data EOT CRC

Transmission

01h 83h 4Bh 7Fh 04h DBh

Response

Not confirmed

Important: After profile reset all profile data are set to auf FFFFFFhex , the current profile number to FFhex.
The display now shows 6 dashes instead of the target.

4.5.2. N 142 restore default, command „Q“ (51h)

This command restores default either of individual or collective parameters.

Data = p (70h) = offset reset

Data = q (71h) = restore default

Data = t (74h) = Assign device identifier 98.

Data = x (78h) = current value reset to 0.

Data = ∆ (7Fh) = All above functions are enabled.

Note: No profile reset. Profile reset by command “R”.

Example 1: Restore default at a specific N 142

SOH Adr Cmd Data EOT CRC

Transmission

01h 20h 51h 7Fh 04h AEh

SOH Adr Data EOT CRC

Response

01h 20h 6Fh 04h 52h N 142 replies by standard response ‚o’ (6Fh) = OK


Example 2: Restore default at all SPAs by broadcast command (identifier = 99)

SOH Adr Cmd Data EOT CRC

Transmission

01h 83h 51h 7Fh 04h B3

Response

Not confirmed