6 examples – Baumer GXP6H User Manual

Page 8

Advertising
background image

Manual_GXP6H_EN.doc

8/13

Baumer IVO GmbH & Co. KG

04.05.11

Villingen-Schwenningen,

Germany

6 Examples

Example 1: Example for a parameter transfer

Host to Encoder

Encoder to Host

Remarks

Control word

Status word

D3

1

D25-

D28

D0-D24 D30-

D31

D25-

D28

D0 -
D24

1

0

0

x

0 0

0

Actual

value

Normal operation

2

0

P. No.

Parameter

0 0

0

Actual

value

Host sends parameter to encoder,
encoder shows no reaction yet

3

0

P. No.

Parameter

0 0

0

Actual

value

Host continues to wait for encoder
confirmation

4

0

P. No.

Parameter

1 1

1)

Para-

meter

Encoder has taken over parameter and
starts processing

5

0

P. No.

Parameter

1 1

1)

Para-

meter

Parameter processing within encoder is
still running

6

0

P. No.

Parameter

1 1

P. No.

Para-

meter

Parameter processing has been finished,
encoder remains in "Parameterization"
state

7

1

0

0

1 1

P. No.

Para-

meter

Device control command "Enable
operation " from Host to encoder. Encoder
shows no reaction yet

8

1

0

0

0 0

0

Actual

value

Encoder is again in "Operation" state

9

0

0

0

0 0

0

Actual

value

Back again to normal operation state of
both participants

1): It must be ensured not to transfer the same parameter number as already confirmed by the encoder when
transmitting a parameter. It is not allowed to repeat the transfer of the same parameter without leaving the
"Parameterization" state.

The parameter number must be consistent.

When transferring several parameters, steps 4 to 6 must be repeated.

It must be ensured when transmitting a parameter that the parameter number is not allotted by the
parameter.

If parameters are transferred that are not valid or do not harmonize, the encoder will turn to the "Disturbance"
state when trying to enable operation.