Dell UPS 1000T User Manual

Page 142

Advertising
background image

ULNM with KVM Virtualized Architecture

142

The following is the command line TCP/UPD for configuration 1 to enable communication between the

Dell ULNM and Dell Network Management Card:

iptables -I OUTPUT -p tcp --dport 80 -j ACCEPT
iptables -I INPUT -p tcp --dport 4679 -j ACCEPT
iptables -I INPUT -p tcp --dport 4680 -j ACCEPT
iptables -I INPUT -p udp --dport 4679 -j ACCEPT
iptables -I INPUT -p udp --dport 4680 -j ACCEPT
iptables -I OUTPUT -p udp --dport 4679 -j ACCEPT
iptables -I OUTPUT -p udp --dport 4680 -j ACCEPT
service iptables save

The following is the command line TCP/UPD for configuration 2 to enable communication between the

Dell ULNM and Dell UPS Network Management Card:

iptables -I OUTPUT -p tcp --dport 80 -j ACCEPT
iptables -I INPUT -p tcp --dport 4679 -j ACCEPT
iptables -I INPUT -p tcp --dport 4680 -j ACCEPT
iptables -I INPUT -p udp --dport 2844 -j ACCEPT
iptables -I INPUT -p udp --dport 2845 -j ACCEPT
iptables -I OUTPUT -p udp --dport 2844 -j ACCEPT
iptables -I OUTPUT -p udp --dport 2845 -j ACCEPT
service iptables save
iptables-save

Dell ULNM Installation (KVM Enabled on RHEL 6 and Debian 5.0)

To install the Dell ULNM on KVM Enabled on RHEL 6 and Debian 5.0:

1 Download the latest version of Dell ULNM for Linux from http://www.dellups.com/.

NOTE:

With Dell ULNM Release 2, you no longer need to download a separate KVM shutdown script. The KVM shutdown

feature is now integrated in standard Dell ULNM Release 2 shutdown script.

2 Select Network solution.
3 Select Linux - Xen - KVM as the Operating Systems.

For RHEL6 x86_64: Download Dell UPS Local Node Manager Release 2, rpm Software Installer

x86_64 for Red Hat (ulnm-linux-x_xx_xxx-x86_64.rpm).

For Debian 5.0 (Lenny): Download Dell UPS Local Node Manager Release 2, deb Software

Installer x86_64 for Debian (ulnm-linux-x_xx_xxx-x86_64.deb).

0120_3-Dell ULNM UG.book Page 142 Saturday, November 2, 2013 5:34 PM