1. When the evaporator and condensing unit are located on the same level,

pipe suction line with inverted trap as shown to prevent liquid migration to the
compressor during the off cycle. Pitch the suction line slightly downward to
the condensing unit:


2. When the evaporator is located below the condensing unit,
a suction trap

must be installed at the evaporator, and an inverted trap must be installed at
the condensing unit, for proper oil return, as follows:


3. When the evaporator is located above the condensing unit, pipe suction line

with inverted trap as shown to prevent liquid migration to the compressor during
the off cycle. The vertical lift of the liquid line is limited to 30 feet. The lift may be
increased to 60 feet if an optional liquid/suction Heat Exchanger is added to the
field piping.