CellarPro 4000SWC SPLIT SYSTEM WATER COOLED, 7649 User Manual

Page 39

Advertising
background image

39

V10.14



Issues

(Cont.) No cooling: no
refrigerant flow.

If the "snowflake" icon is
illuminated on the
temperature display
control, the compressor
should be running.











Possible Causes



Potential Solutions

(Cont.) High
pressure safety
shutdown / high
discharge
pressure

Fouled water cooled condenser coil, consult
factory.

Intermittent power
to compressor

Check for loose wires and secure.

Compressor cycling on internal thermal overload
protection. Replace start capacitor/relay
assembly

Compressor cycling on high pressure - see "High
pressure safety shutdown" section.

Faulty compressor. Consult factory.

No cooling: Evaporator
fan not blowing.

If the "fan" icon is
illuminated on the
temperature display
control, the fan should be
blowing air.

No power to fan(s)

Power supply to Evaporator interrupted. Restore
power.

Power supply to fan interrupted: loose wire.
Inspect for loose fan wiring and reconnect.

Fan capacitor: check for loose wires or out of
spec capacitance. Reconnect loose wires or
replace capacitor(s).

Fan obstructed

With power to unit disconnected, check the
rotation of the blower fan. If fan does not spin
freely, inspect for and remove obstructions. If no
obstructions are found, the fan may need to be
replaced. Consult factory.

Fan running but
not drawing air
through coil.

Fan short cycling: Make sure all housing panels
are attached to the unit. Replace missing panels.

Coil is blocked with ice. Refer to the "Iced coil"
section.

Iced coil

Temperature
displayed is higher
than actual cellar
temperature

If using a bottle probe, check placement and
compare to actually cellar temp. Relocate probe
if necessary to better correlate to actual cellar
temperature.

Probe fault: check for loose connections if
splices were added in the field.

Moisture in bottle probe jack: Can cause high
readings, consult factory for solution.