Up and Down Buttons

To view the “High Temp” recorded by the
cooling unit, press

the “Up” button once.

To view the “Low Temp” recorded by the
cooling unit, press

the “Down” button once.


To reset

the “High Temp” or “Low Temp”,

press

the “Set” button for three seconds

while “Hi” or “Lo” is displayed. “RST” will
blink three times to indicate confirmation.

Set Button

The cooling unit is factory preset with a
Minimum Set Point of 58°F and a
Temperature Differential of 4°F. This means
that the cooling unit will turn on when the
display rises above 62°F (58°F + 4°F), and
turn off when the display falls below 58°F.
In this example, the average temperature
inside the cellar will be 60°F.

To view the Minimum Set Point, press the
“Set” button for one second.

To change the Minimum Set Point,

Press

the “Set” button for three

seconds until °F” blinks

Press

“Up” or “Down” button

Press

“Set” button to confirm


The “Set” temperature will blink three times
to indicate confirmation

The recommended Minimum Set Point
range is 53 - 60°F. To change the
Temperature Di

fferential, see “Advanced

Operation” later in this chapter.