ENGLISH INSTRUCTIONS

Installation Instructions

1. Consult local codes for specific installa-

tion requirements and restrictions appli-

cable to your area. It is recommended

that system supply pressure be at least

20psi (133kPa).

2. These instructions apply to Series 850,

LF850 (DC), 856, LF856 and 856ST

(DCDA), sizes 2

1

2

" to 10" only (65 –

250mm). The valves may be installed

only in the orientation/flow direction as

shown. The gate valves may be rotated

as permitted by the flange bolt pattern

on vertical installations only.

3. The valve assembly must be installed

where it is accessible for periodic

testing and maintenance. Clearances

shown in the installation views apply

to exterior, interior and pit/vault instal-

lations and are only recommendations.

These minimums do not apply to

removable protective enclosures. Refer

to local codes for actual requirements in

your area.

4. PRIOR TO INSTALLING THE VALVE

INTO THE LINE, FLUSH THE SUPPLY

LINE OF ALL FOREIGN MATERIAL.

Failure to flush the supply line may

cause the check valves to become

fouled and require disassembly and

cleaning.

5. Lift the assembly by connecting lift

hooks to the lift rings cast into

the valve body. DO NOT LIFT THE

ASSEMBLY BY CONNECTING TO

THE GATE VALVE HANDWHEELS OR

STEMS.

6. After installation SLOWLY fill the

assembly with water and bleed air

from the body using the # 3 and # 4

test cocks. Test the valve assembly to

ensure correct operation.

NOTICE

All assemblies are tested at the factory for

proper operation and leakage. If the valve

does not pass the field test, it is most like-

ly due to a fouled check valve. This is not

covered by the factory warranty. The valve

cover(s) must be removed and the check

seats inspected and cleaned. Any damage

or improper operation caused by pipeline

debris or improper installation/start-up is

not included in the factory warranty.
In case of a possible warranty claim,

contact your local supplier or FEBCO

Representative. DO NOT REMOVE THE

VALVE ASSEMBLY FROM THE PIPELINE.

7. The assembly must be protected

from freezing and excessive pressure

increases. Thermal expansion or water

hammer can cause pressure increases.

These excessive pressure situations

must be eliminated to protect the valve

and system from possible damage.

Local building or plumbing codes may require modifications to the information provided.

You are required to consult the local building and plumbing codes prior to installation. If

this information is not consistent with local building or plumbing codes, the local codes

should be followed.
Need for Periodic Inspection/Maintenance: This product must be tested periodically in

compliance with local codes, but at least once per year or more as service conditions war-

rant. Corrosive water conditions, and/or unauthorized adjustments or repair could render

the product ineffective for the service intended. Regular checking and cleaning of the

product’s internal components helps assure maximum life and proper product function.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can

result in death, serious personal injury, property damage, or

damage to the equipment.
Keep this Manual for future reference.