Servicing check valve assemblies general, Troubleshooting for double check assemblies, Disassembling the check valve – FEBCO 856ST MasterSeries In-Line Design Double Check Detector Assemblies User Manual

Page 4: Test procedure

Advertising
background image

4

Servicing Check Valve Assemblies

General

FEBCO recommends yearly maintenance. Consult your local codes for requirements in

your area.
1. Detailed maintenance manuals

are available from your local Febco

representative.

2. Rinse all parts with clean water prior to

reassembly.

3. DO NOT USE ANY PIPE DOPE, OIL,

GREASE OR SOLVENT ON ANY PARTS

unless instructed to do so.

4. Do not force parts. Parts should fit

together freely. Excess force may

cause damage and render the assembly

inoperable.

5. Carefully inspect seals and seating

surfaces for debris or damage.

6. After servicing, repressurize the

assembly and test to ensure proper

operation.

Troubleshooting for Double Check Assemblies

PROBLEM

CAUSE

SOLUTION

1. Check valve leaking

a. Debris on seating surface

Disassemble and clean

b. Leaking shutoff valve.

Disassemble and clean

2. Low flows passing through

a. Mainline check fouled

Disassemble and clean

b. Bypass line plugged

Disassemble and clean

Disassembling the Check Valve

1. Close the outlet shutoff valve, then

close the inlet shutoff valve. Bleed

residual pressure from the assembly by

opening the #4, #3, and # 2 test cocks

in this sequence.

2. Remove the cover bolts/nuts and lift

the cover from the body. The springs

are retained and the cover should be

pushed away from the body approxi-

mately

1

4

inch.

3. Inspect/clean debris from the disc and

seat ring. Replace worn or damaged

parts as required.

4. Replace the cover, ensure the spring

assembly is positioned in the pivot sock-

et. If necessary, apply FDA approved

grease to the O-ring groove in the body

to keep the O-ring in position while

installing the cover.

5. Install the bolts and nuts and tighten.

Test Procedure

FEBCO recommends the use of

the appropriate annual test method

presented in the ASSE Series 5000

manual that is consistent with your

local codes.

Advertising