Analog Output Card Installation

5

Figure 3. Analog Output Menu

2. Connect multimeter to connector J1 on the analog output card:

• For voltage output, connect voltmeter leads to pins 3 (-) and 4 (+)

• For current output, connect ammeter leads to pins 1 (-) and 2 (+)

3. Adjust zero calibration: Scroll to the TWZERO parameter. Press to view zero value, then check voltage or

current reading on multimeter. Enter this reading as follows:

• Press or to select the digit.

• Press or to increment or decrement the value.

• Press

TARE

when the value is correct.

4. Adjust span calibration: Scroll to the TWSPAN parameter. Press to view span value, then check voltage or

current reading on multimeter. Enter this reading as follows:

• Press or to select the digit.

• Press or to increment or decrement the value.

• Press

TARE

when the value is correct.

5. Final zero calibration: Return to the TWZERO parameter and verify that the zero calibration has not drifted.

• Press or to select the digit.

• Press or to increment or decrement the value.

• Press

TARE

when the value is correct.

6. Return to normal mode. Analog output function can be verified using test weights.

See the 880 Installation Manual (PN 152240) for more configuration information.