Wiring diagram, load cells in hazardous areas, 4 load cell wiring for hazardous environments, Revisions rev reference init da te – Rice Lake Load Cells - Wiring for Hazardous Environments User Manual

Page 7

Advertising
background image

4

Load Cell Wiring for Hazardous Environments

3. MTL BARRIERS ARE MANUF

ACTURED IN ENGLAND;

REP

. IN USA : MTL INC., 8576 WELLINGTON ROAD, MANASSAS, V

A. 22110.

MORE THAN 250 VOL

TS RMS.

2. ELECTRICAL EQUIPMENT CONNECTED TO BARRIER INPUTS SHOULD NOT USE OR GENERA

TE

1. DRAWING REVISIONS MUST BE APPROVED BY F

ACTOR

Y MUTUAL PRIOR TO RELEASE.

NOTE:

4. R. ST

AHL BARRIERS ARE MANUF

ACTURED A

T

150A NEW BOSTON ST

., WOBURN, MA. 01801.

6. RICE LAKE WEIGHING SYSTEMS MANUF

ACTURES JUNCTION BOXES AND BARRIER BOXES.

JUNCTION BOXES : EL604ST

A, EL604STR, EL604ET

A, EL210, EL211A, AND JB808.

BARRIER BOXES : BBX-XX SERIES.

REP

. IN USA : PEPPERL & FUCHS INC., 1600 ENTERPRISE P

ARKW

A

Y, TWINSBURG, OHIO. 44087.

5. PEPPERL & FUCHS BARRIERS ARE MANUF

ACTURED IN GERMANY

.

IN THE NON-HAZARDOUS AREA. GROUNDING PRACTICES SHOULD CONFORM TO NEC AR

TICLE 250.

7. THE BARRIER MUST BE GROUNDED VIA TWO INDEPENDENT CONNECTIONS TO A GROUND ELECTRODE

THE RESIST

ANCE FROM THE BARRIER TO THE GROUND ELECTRODE MUST NOT EXCEED ONE OHM.

8. MAINS POWERED EQUIPMENT CONNECTED TO THE NON-HAZARDOUS AREA TERMINALS

MUST BE ISOLA

TED FROM THE MAINS SUPPL

Y BY A DOUBLE WOUND TRANSFORMER, UNLESS

THE APPLICABLE ELECTRICAL CODE PERMITS MUL

TIPLE GROUNDING OF THE NEUTRAL LEAD.

9. WIRING CONNECTED TO HAZARDOUS AREA TERMINALS MUST BE SEPERA

TED

FROM NON-INTRINSICALL

Y SAFE WIRING.

CABLE USED ARE NOT KNOWN, V

ALUES OF 60 PICOF

ARAD PER FOOT AND .2 MICROHENERIES PER FOOT MA

Y

FOR THE P

A

R

TICULAR BARRIER MUST NOT BE EXCEEDED. IF THE CAP

ACIT

ANCE AND INDUCT

ANCE OF THE

10. ALL WIRING HAS DISTRIBUTED INDUCT

ANCE AND CAP

ACIT

ANCE. THE MAXIMUM PERMITTED CABLE P

ARAMETERS

BY USED AS CONSER

V

A

TIVE CRITERIA FOR DETERMINA

TION OF CABLE AFFECTS.

SHALL NOT BE RUN IN THE SAME CABLE, UNLESS A

T

LEAST .25 mm THICKNESS INSULA

TION

CABLE. DIFFERENT INTRINSICALL

Y SAFE CIRCUIT OF THE SAME INTRINSICALL

Y SAFE SYSTEM

11. DIFFERENT INTRINSICALL

Y SAFE SYSTEMS SHALL NOT BE RUN IN THE SAME MUL

TICONDUCTOR

IS USED ON EACH CONDUCTOR, OR UNLESS NO HAZARD RESUL

TS FROM INTERCONNECTION.

IF IN DOUBT

, CONT

ACT THE LOCAL INSPECTION AUTHORITY

.

GAS, V

APOR, OR DUST

. REFER TO NFP

A 325 FOR IGNITION LISTINGS.

AT

A TEMPERA

TURE IN EXCESS OF THE IGNITION TEMPERA

TURE OF THE SPECIFIC

12. HAZARDOUS AREA EQUIPMENT SHALL NOT HA

VE EXPOSED ANY SURF

ACE THA

T OPERA

TES

DO NOT INCLUDE THE CAP

ACIT

ANCE AND INDUCT

ANCE OF THE CABLE

WITH OTHER FM ENTITY CER

TIFIED BARRIERS OR INTERF

ACES. THE ENTITY P

ARAMETERS SHOWN

13. THESE LOAD CELLS SHALL BE USED IN CONJUNCTION WITH DEVICES LISTED ON T

ABLE I OR

Vmax. = 27 V

Imax. = 400 mA

Ci = 0.0 micr

ofarads

Li = 0.0 micr

oheneries

THE POLARITY OF THE NON-HAZARDOUS APP

ARA

TUS AND SELECTED BARRIERS.

14. POLARITY OF THE HAZARDOUS AREA TERMINALS ARE DETERMINED BY

SINGLE OR DUAL (AC) OR (DC) BARRIERS WITH THE SAME POLARITY MA

Y BE MIXED

APPLICA

TIONS (AC) MA

Y BE UTILIZED IN DC APPLICA

TIONS IN LIEU OF POLARIZED BARRIERS.

16. ALL BARRIERS MUST BE OF THE SAME POLARITY

. BARRIERS UTILIZED FOR NON-POLAR

IF BARRIER POLARITIES ARE IN COMPLIANCE WITH ITEM "C".

15. LOAD CELL POLARITIES FOR EXCIT

A

TION AND SIGNAL MA

Y BE REVERSED

UNUSED SENSE WIRES OR CONNECT THE SENSING LEADS TO THE EXCIT

A

TION LEAD

18. APPLICA

TIONS NOT REQUIRING EXCIT

A

TION SENSING, SHALL EITHER TERMINA

TE AND INSULA

TE

OF THE SAME POLARITY

.

OR SUBSTITUTED. FOR SPECIFIC BARRIER TYPES REFER TO SHEET 2.

17. LOAD CELL MODEL NUMBERS COVERED BY THIS DRAWING:

RL1010

RL1040

RL1250

RL1140

RLETO

RL30000D

RLHBB

RL1521A

RL1260

RL1042

RLHTO

RL75058A

SCALE

TREA

TMENT

ANGLE

3 PLC

2 PLC

TOL.

DECIMAL

DRAWING TOLERANCES

TITLE

SHEET OF

DWG NO

THIS DRAWING AND ALL INFORMA

TION CONT

AINED HEREIN IS AND REMAINS

THE PROPER

TY OF RICE LAKE WEIGHING SYSTEMS INC. AND IS CONFIDENTIAL.

IT IS SUBMITTED AND MA

Y BE USED ONL

Y IN CONNECTION WITH RICE LAKE

WEIGHING SYSTEMS' PROPOSAL AND/OR ITS CUSTOMERS' ORDERS. IT SHALL NOT BE

DISCLOSED TO OTHERS OR COPIED WITHOUT RICE LAKE WEIGHING SYSTEMS' SPECIFIC

WRITTEN CONSENT AND SHALL BE IMMEDIA

TEL

Y RETURNED UPON REQUEST

.

REVISION

REVISIONS

REV

REFERENCE

INIT

DA

TE

ALL THREADS TO BE CLASS 2

UNLESS OTHER

WISE SPECIFIED

ALL DIMENSIONS APPLICABLE AFTER TREA

TMENT

UNLESS OTHER

WISE SPECIFIED

DO NOT SCALE

DRAWING

SURF

ACE

FINISH

MA

TERIAL

THIRD ANGLE PROJECTION

UNITS TO BE INCHES

FOR RL

WS

USE ONL

Y

RICE LAKE WEIGHING SYSTEMS

MFG.ENG.

DR.BY

APPROVED

DES.ENG.

APPROVED

CKD.

WIRING DIAGRAM,

LOAD CELLS IN HAZARDOUS AREAS

66090

1:1.5

19

---

---

---

---

---

---

NEW

PJM 10/5/00

PJM 10/5/00

DFH 10/5/00

0