Junction Box and Grounding

9

Be certain each load cell grounding strap is securely connected to the top plate and bottom plate of each load cell

mount. There should be metal-to-metal contact with no presence of paint or grout. This strap is designed to channel

power surges on the deck around—rather than through—the load cell to ground.

Grounding
Strap

Figure 3-2. Grounding strap on load cell mount.

These, and all, ground connections must be torqued to a specified value and retorqued at regular service intervals.

A thick coating of anti-oxidant grease should be maintained on all ground connections to prevent corrosion.
A separate grounding system conductor must extend uninterrupted from the main service panel ground to the scale

to protect load cells and scale wiring from lightning and other transient damage. This ground wire conductor must

be an unsheathed #10 copper wire or larger. Run the bare ground wire conductor intact from the AC power ground

rod to the scale in a separate trench. Bring the wire up from the trench near the junction box and attach it to the

ground lug of the junction box. A #10 bare ground wire is run from the ground lug of the junction box to one of the

junction box mounting studs on the scale frame, thus grounding the scale frame to the same single-point ground as

the AC power for the indicator.
.

ground before indicator

Figure 3-3. Junction box ground wire connections.