3 electrical connections, Sct-30 – Rice Lake SCT-30 User Manual

Page 10

Advertising
background image

6

SCT-30 Weight Transmitter Manual

1.3

Electrical Connections

• It is recommended that the negative side of the power supply be grounded.
• It is possible to power up to eight 350 ohm or sixteen 700 ohm load cells.
• Connect terminal “0 VDC” to the RS-485 common of the connected instruments

in the event that these receive alternating current input or that they have an opto-
isolated RS-485.

Figure 1-2. Wiring Diagram

SCT-30

13

1 2 3 4 5 6 7 8 9

11 12

10

14 15 16

LOAD CELLS IN PARALLEL(1-16 terminals)

+ EX

-

EX

-

SIG

+ SIG

+ EX

-

EX

-

SIG

+ SIG

+ EX

-

EX

-

SIG

+ SIG

MODE

FILTER

DIP-SW

MODIFY
and
CONFIRM

23

22

20

18 19

21

17

+12-24

POWER

VDC

0

V

mA COM -

+

RS485

-

+

ZERO

NORMAL

FS CAL

1 2 3

ON

1

3

2

ON

YELLOW

GREEN

RED

EXCITATION -

EXCITATION +

SIGNAL -

SIGNAL +

EXCITATION -

EXCITATION +

SIGNAL -

SIGNAL +

EXCITATION -

EXCITATION +

SIGNAL -

SIGNAL +

EXCITATION -

EXCITATION +

SIGNAL -

SIGNAL +

Current output: max load 400 ohm

Voltage output: min load 2 kohm

+

+ +

+

-

- -

RS485

ANALOG
OUTPUT

12/24 Vdc

SUPPLY

+ SUPPLY

- SUPPLY

1

22

3

1: Selector switch

2: Knob control

3: DIP switch

Advertising