3 alarms – Rice Lake SCT-30 User Manual
Page 17
RS-485 Serial Connection 13
H&L DIVISIONS (40008-40009)
For additional examples regarding the generation of correct control characters
(CRC16) refer to the manual Modicon PI-MBUS-30.
3.3
Alarms
ANALOG OUTPUT VALUE UNDER ALARM CONDITIONS
Status Register (40007)
Bit 0
Cell Error (ERCEL)
Bit 1
AD Convertor Malfunction (ER AD)
Bit 2
Off scale analog output (ER OL)
Bit 3
Bit 7
Division negative sign
Bit 11
Weight stability
Bit 12
Display
Description
ErCEL
Load cell is not connected or is incorrectly connected; the load cell signal
exceeds 39 mV; the analog output generates the lowest possible value.
Er OL
The calculated analog signal is outside the allowed generating range:
Er Ad
The conversion electronics is malfunctioning, the analog output generates
the lowest possible value; check load cell connections, if necessary
contact technical assistance.
ANALOG OUTPUT TYPE
Minimum
Maximum
0-10 V
-1.000
11.000
0-5 V
-1.000
5.500
-10-10 V
-11.000
11.000
-5-5 V
-5.500
5.500
0-20 mA
0.000
24.000
4-20 mA
0.000
24.000