4 analog output type selection, Sct-30, 10 mv to the selected analog output value – Rice Lake SCT-30 User Manual
Page 11
Introduction
7
Figure 1-3. RS-485 Serial Connection
If the RS-485 network is longer than 100 meters or baud rates higher than
9600 are used, connect two 120 ohm terminating resistors between the
‘+’ and ‘–’ terminal strip ends of the instruments farthest away. Should
there be different instruments or converters, refer to the specific manuals
to determine whether it is necessary to connect the above-mentioned
resistors.
1.4
Analog Output Type Selection
Set the indicated DIP switch with MODE.
By default, the instrument is calibrated to convert the load cell 0
-
10 mV to the
selected analog output value.
By modifying the type of analog output, calibration will be brought back
to default values.
DIP SWITCH
OPERATION MODE
1
2
3
OFF
OFF
OFF
0-5 V
OFF
OFF
ON
0-10 V
OFF
ON
OFF
-5-5 V
OFF
ON
ON
-10-10 V
ON
OFF
ON
4-20 mA (default)
ON
ON
OFF
0-20 mA