Diagnostic Faults:

The following is a list of the diagnostic faults, with a brief explanation of each.

String Class

Meaning

uLu CTrL

Alarm

The control valve feedback is invalid, indicating the system is not
under control. Voltage and/or Frequency may be out of
specifications.

xI Cvrr

Override Over-current condition. The line in which the over-current

condition exists is indicated by the location of the “

xI” string: If in

the “Amps Line 1” field, the over-current is in line 1; If in the
“Amps Line 2” field, the over-current is in line 2.

bAd (r 1

Alarm

Current sensor fault on line 1. The indicated current may be
incorrect.

bAd (r 2

Alarm

Current sensor fault on line 2. The indicated current may be
incorrect.

bAd uoLT

Override

Voltage Sensor Fault. The indicated voltage may be incorrect.

OIL xoT

Alarm

Oil temperature is getting too high (>175° F). Measured
Temperature in the “Hours” field

OIL xoT

Override

Oil Temperature is too high (>180° F). Measured Temperature
in the “Hours” field.

Add 0IL L0

Override

Oil level in reservoir is low. Add oil to clear the error.

OIL xoT

Shutdown Oil Temperature dangerous (>220° F). Measured Temperature

in the “Hours” field.

bAd Ind

Alarm

Indicator Light Ground Fault. The indicator light may not
function properly.

bAd tSnS

Alarm

Temperature Sensor Fault. The indicated oil temperature may
be incorrect.

bAd ALrt

Alarm

Buzzer Ground Fault. The audible alert buzzer may not function
properly.

bAd dISP

Alarm

Display Ground Fault. The Command & Control Center may not
operate properly.

LS FAn

Alarm

Low Side Fan Short. The Fan may not operate properly

0IL FILT

Service

Warning /

Override

Service Warning: Change the Oil Filter

UNB LOAD

Override There is an electrical load imbalance of more than 20% of the

systems’ rating between Line 1 and Line 2

Table 2