WARNING

The boiler must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirements, with the latest edition of the national

Electrical Code, ANSI/NFPA 70, in the U.S. and with

the latest edition of CSA C22.1 Canadian Electrical

Code, Part 1, in Canada. Do not rely on the gas or

water piping to ground the metal parts of the boiler.

Plastic pipe or dielectric unions may isolate the boiler

electrically. Service and maintenance personnel who

work on or around the boiler may be standing on wet

floors and could be electrocuted by an ungrounded

boiler.

AVERTISSEMENT

La chaudière doit être mis à la terre conformément

aux prescriptions de l'autorité ayant juridiction ou,

en l'absence de telles exigences, avec la dernière

édition du national Electrical Code, ANSI/NFPA

70, aux ÉTATS-UNIS et à la dernière édition de la

norme CSA C22.1 Code électrique canadien, partie

1, au Canada. Ne pas compter sur le gaz ou l'eau

tuyauterie à la masse des pièces métalliques de la

chaudière. Tuyau en plastique ou diélectrique les

syndicats peuvent isoler la chaudière électrique.

SECTION 6.

6A. Electrical Wiring

Follow these instructions to make the necessary

initial electrical connections.
1. Remove the two screws attaching the front cover

of the control box.

2. There are wires coiled in the area on the right

side of the control box, supplied with wire nuts:

black wires and white wires.

3. Follow the schematic in Figures 14A. and 14B.

Remove the wire nut from the two sets of wires,

and connect the hot lead from the 115V power

supply, and the neutral lead to the white wires.

4. Attach the leads from the wall thermostat to

the terminal strip, located on the left side of the

control box.

5. Check the boiler wiring and pump for correct

voltage, frequency and phase. If the pump circuit

is other than 115V, be sure there is an appropriate

transformer or relay installed. The pump relay is

suitable for pumps of 1/3 HP or less (max 5A).

6. For systems with multiple zone pumps or valves

(see Figure 17).

A means of disconnecting the electrical supply must

be provided within sight of the boiler. The pump and

boiler must be wired as shown to insure that the pump

is running whenever the boiler is firing.

Flow Switch: If the system includes a flow switch,

it should be wired in series with the high-limit switch.

The boiler will not fire unless the pump is running and

the flow switch is closed.

Field installed safety devices and operating

controllers, such as valve end switches, relays, timers,

can be connected to the boiler through the wall

thermostat circuit. Do not exceed a draw of 40VA on

the transformer secondary. A 2-Amp fuse is here to

protect the transformer.

6B. Outdoor Reset.

To comply with Federal Law, the Brute Mini JV

automatically sets water temperature based on outdoor

temperature. A sensor (E2347400) supplied must

be located outdoors yet out of direct sunlight. If not

connected, the boiler may not be fully functional.

Connect the sensor to the terminals labeled "COM"

and "OUTDOOR" located on the left side of the

control box, using outdoor rated min 24 gauge wire.

(See Figures 13A and 13B)

Figure 13B

Figure 13A

Terminals