Beckett AquaSmart Wiring User Manual

Page 13

Advertising
background image

13

AquaSmart Boiler Control Wiring Guide

Control Programming

- for optimal energy savings

AquaSmart A or B with Honeywell V8043E/V8044E zone valves & main zone circulator

(with or without tankless H/W coil)

1. High Limit: 180
2. High Differential: 10
3. Low Limit: “OFF”
4. Set DHWP to “OFF”

5. Low Limit: 160 (with tankless H/W coil)

6. Low Differential: 10

7. Set Circulator on “TT”

8. Circulator On-Delay: “30 Seconds”
9. Circulator Off-Delay: 4 minutes
10. Set Economizer to “ON”
11. Set Effi ciency “HI”