Control Programming

- for optimal energy savings

Technology Made Simple.

AquaSmart A or B Taco SR503 zone panel & indirect H/W circulator

1. High Limit: 180
2. High Differential: 10
3. Set DHWP to “TT”
4. Set Circulator on “TT”
5. Circulator On-Delay: “OFF”
6. Circulator Off-Delay: 2 - 4 Minutes

7. Set Economizer to “ON”
8. Set Effi ciency “HI”