Control Programming

- for optimal energy savings

Technology Made Simple.

AquaSmart A or B multi-zone connections with main zone circulator

(with or without tankless H/W coil)

1. High Limit: 180
2. High Differential: 10
3. Low Limit: “OFF”

4. Low Limit: 160 (with tankless H/W coil)
5. Low Differential: 10

6. Set DHWP to “OFF”

7. Set Circulator on “TT”
8. Circulator On-Delay: “OFF”
9. Circulator Off-Delay: 4 Minutes
10. Set Economizer to “ON”
11. Set Effi ciency “HI”