AquaSmart Boiler Control Wiring Guide

Table 2 - Functional Replacement (Advanced Wiring Needed)

Note: Available operating limit and/or differential ranges may not be equivalent. Compare settings to the AquaSmart
ranges before replacing.

AquaSmart Cross-Reference Guide - Functional Replacements

Honeywell

L4006A (All)

L4006G 1022

L4006H 1004

L4008A (All)

L4080B,D

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for

operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to OFF. ● To use with a millivolt system an

appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.

L4006E (All)

L4008E (All)

L4080F,G

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Requires the addition of a manual-reset high limit. ● Make sure 7600 outputs do not exceed 7.4A @ 120VAC. ● 7600 outputs

are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are

unused. ● Set low limit on 7600 to OFF. ● To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must

be added to switch the millivolt circuit.

L6006A (All)

L6006C 1018

L6008A 1192

L6008A 1242

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. ● To use with a millivolt system an appropriate

voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. ● Make sure 7600 outputs do not exceed 7.4A @ 120

VAC. 7600 outputs are not rated for 240 VAC. ● 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC,

and ZR are unused. ● Set low limit on 7600 to OFF.

L8124B 1039

L8148J 1009

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. 7600 outputs

are not rated for 240 VAC.

L7148F (All)

L8148E (All)

Replace with AquaSmart

7600B

Must confi rm that 7600 VA rating is adequate to meet VA requirements of system. ● Make sure 7600 B1 output does not exceed 1.25A @ 24VAC

(30 VA). ● 7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z, respectively. ● If damper is used, consult

damper manufacturer’s wiring instructions for using damper without damper plug.

L4081A/B

L6081A/C

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Remove switching relay, if used, from the system when replacing the L4081 or L6081. ● Make sure 7600 outputs do not exceed 7.4A@120VAC.

7600 outputs are not rated for 240 VAC.

Carlin

90200A

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.

90000

(All)

90200E

90200EL

90300B

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Requires the addition of a manual-reset high limit. Make sure 7600 outputs do not exceed 7.4A. ● Set low limit on 7600 to OFF.

90200D

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. Make sure 7600 outputs do not exceed 7.4A.

Set low limit on 7600 to OFF.

White Rodgers

11B06-1

11D18-1

11B18-101

11B30-104

11B02-1

1145-33

11B06-46

11B95-31

11B18-153

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an additional wire (L2) for

operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to OFF.

11D82-1

11D31-1

1131-102

1127-2

11A79-2

1127-9

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. 7600 outputs are not rated for 240 VAC. ●

7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on 7600 to

OFF.

11B27-9

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

Requires the addition of a manual-reset high limit. ● Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240

VAC. 7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused. ● Set low limit on

7600 to OFF.

8J48A-209

Replace with AquaSmart 7600A or 7600B

(Based on System Voltage Requirements)

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt

circuit.