Important, Initial set-up, Dimensions – Steffes 4140 Owner & Installers Manual User Manual

Page 11: Back and sides = 3 inches, Bottom = 0 clearance top = 6 inches, Front = 36 inches, For ease in servicing), Return and supply)

Advertising
background image

Comfort Plus

Installation

3.03

Installation

4100 SERIES SYSTEM REQUIREMENTS

FIGURE 3

CLEARANCES

INITIAL SET-UP

Step 1

Remove the Information Package from the
outside of the shipping box and unpackage the
Comfort Plus heating system.

Step 2

Remove the heating elements from inside the
base of the system.

Step 3

Move the system into its installation location.
The Comfort Plus is capable of fitting through
a 30" doorway (minimum) without disassem-
bling. If necessary, the 4100 series can be
disassembled for ease in moving. To disas-
semble the 4100 Series Comfort Plus, refer to
the disassembly instructions (Page A.02) for
more information.

The 3100 series can NOT be disassembled.

IMPORTANT

Risk of improper operation or equipment dam-
age. Read and follow installation instructions
carefully.

Remove the Comfort Plus system from its
shipping pallet before installing.
Leveling legs should be extended no more
than one inch.
DO use and follow generally accepted safety
practices when handling insulation material.
DO have equipment installed by a qualified
technician in compliance with all applicable
codes and regulations.

3A

FRONT VIEW

48"

2" MIN

CLEARANCE

(IN COLD AIR RETURN)

6" X 6" REGISTER

FILTER TRAY

0" REQUIRED

CLEARANCE

M

S TEFF ES

P

M

M

A

0" REQUIRED

CLEARANCE

6" MIN CLEARANCE

3 B

TOP VIEW

36" MIN CLEARANCE

3" MIN CLEARANCE

DIMENSIONS

P
M

(4100 Series)

18" Standard

22

1
2

" if 1hp

Front View

29

3

16

13

3
4

± 1/4"

14±1/4

4100 Series

Top View

10

1
2

22

5

16

Electrical

Panel

26

3

16

"

28

3

16

"

20

1
4

49

7

16

" Standard

53

15
16

" if 1hp

24

3
4

" if 1hp

4140

68

5

8

"

4130

57

5

8

"

4120

46

5

8

"

25

1

16

"

24

1
4

"

Return Air Plenum

(Order Item

#1301550)

22

1
4

"

22 5/8"

Supply Air Plenum
(Factory Supplied)

44

11

16

"

8 3/8"

(± 1/4")

22 5/8"

M

A

M

S TE FFES

Back and Sides = 3 inches

(from combus-

tible material)

Bottom = 0 clearance
Top = 6 inches

(from combustible material)

Front = 36 inches

(for ease in servicing)

Between Duct and Left Side of System =
2 inches
Between Duct and Right Side of System =
0 clearance
Outer Sides of System Ducts

(Return and

Supply)

= 0 clearance

IMPORTANT:
Return air duct
MUST NOT enter
from the front or
back of the furnace.
Upflow, downflow, or
straight return
ducting only.

3D

3C

Minimum clearance requirements may NOT account for required working space for
electrical connections.