Heat Pump Booster

Function: Core Charging

Problem: Unit will not charge (Unit has no core charge) or Control Board lights are off.

Before starting any of the procedures below, check voltage on load side of all HPB circuit breakers and

check low voltage fuses on charge control circuit board. Place unit in off-peak mode.

Check utility switch and HPB off-peak

light on charge control circuit board

(51) for proper operation.

Check "Outdoor Temperature

Sensor" lights on charge

control circuit board (51).

Check "ETS CHARGING"

indicator light on charge

control circuit board (51).

Check for 24 VAC on orange

wire going to the top of the

staging sequencer (50).

Lights Operable

Off

On

Jumper thermostat (53) brown

lead to thermostat orange lead.

(NOTE: Make sure thermostat

shaft is in full clockwise position.)

Check unit wiring

and/or replace

charge control

circuit board (51).

Check for defective

charge sequencers

(58) or defective

heating elements (18).

Check for 24 VAC between each of

the two bottom low voltage fuses

and the "C" position (thermostat

connection), on charge control

circuit board's terminal block.

Voltage
Present

No Voltage

Lights Inoperable

Replace thermostat (53).

Replace charge control

circuit board (51).

Check outdoor temperature and

refer to the Theory of Operation

in Appendix of the Owner's

Manual.

Charge light on

Charge light off

One or more

lights on

No

Lights

Check line voltage supply to

control transformer (55) and

unit wiring.

Replace charge control

circuit board (51).

Voltage not

present on one

or both

Both fuses

energized

Set the charge level selector switch on

the charge control circuit board (51)

to the "HIGH" position and retest.

With charge control circuit board switches in
"AUTO" and "WINTER" position:

1. Remove outdoor sensor wire "G". Outdoor
temperature light #1 should be on.

2. Remove outdoor sensor wire "B". Outdoor
temperature light indicator #2 should be on.

Below 45º

Outdoor

Temperature

Above 45º

Outdoor

Temperature

Replace outdoor air

temperature sensor (61).

Replace charge control

circuit board (51).

Ok

Defective

Repair wiring.

Defective

Check in-line fuse in
transformer secondary
wiring.

Ok

Look for shorts in low
voltage wiring and replace.

Open

Good

Flow chart

continued on

next page.

Page 1

Check utility switch and HPB off-peak

light on charge control circuit board for

proper operation.

Check "Outdoor

Temperature Sensor"

lights on charge control

circuit board.

Check "ETS CHARGING"

indicator light on charge

control circuit board.

Check for 24 VAC between "C"

terminal on SFIII board and on
orange wire going to the top of

the staging sequencer.

Lights Operable

On

Jumper thermostat brown lead to

thermostat orange lead. (NOTE:

Make sure thermostat shaft is in

full clockwise position.)

Check unit wiring

and/or replace

charge control

circuit board.

Check for defective

charge sequencers or

defective heating

elements.

Check for 24 VAC between each of

the two bottom low voltage fuses

and the "C" position (thermostat

connection), on charge control

circuit board's terminal block.

Voltage
Present

No Voltage

Lights Inoperable

Replace charge

control thermostat.

Replace charge control

circuit board.

Check outdoor temperature

and refer to the Theory of

Operation.

Charge light on

Charge light off

One or more

lights on

No

Lights

Check line voltage supply

to control transformer and

unit wiring.

Replace charge control

circuit board.

Voltage not

present on one

or both

Both fuses

energized

Set the charge level selector switch on

the charge control circuit board to the

"HIGH" position and retest.

With charge control circuit board switches in
"AUTO" and "WINTER" position:

1. Remove outdoor sensor wire "G". Outdoor
temperature light #1 should be on.

2. Remove outdoor sensor wire "B". Outdoor
temperature light indicator #2 should be on.

Below 45º

Outdoor

Temperature

Above 45º

Outdoor

Temperature

Replace outdoor air

temperature sensor.

Replace

charge control

circuit board.

Ok

Defective

Repair wiring.

Defective

Check in-line fuse in

transformer secondary

wiring if equipped.

Ok

Look for a short circuit

in low voltage wiring

and replace transformer

if necessary.

Good

Off

Open

Check slam gate

assembly behind the

units inlet/outlet

ducting ports.

Held Shut

Opens

Freely

Replace melt links and

complete discharge air

check-out procedure.

Check slam gate

interlock switch.

Adjust or replace.

Check secondary voltage

(approximately 24 VAC)

at the transformer.

Replace

Transformer.

Replace Charge

Control Circuit

Board.

Closed

Open

Proper voltage

present

No

Voltage

Opens

Freely