Steffes HPB22 Troubleshooting Guide User Manual

Page 5

Advertising
background image

Page 3

Heat Pump Booster

Function: Core Charging

Problem: Unit overcharges on warm days

Before starting any of the procedure below, check voltage on load side of all HPB circuit

breaker and check low voltage fuses on charge control circuit board.

Check operation of the three

"Outdoor Temperature

Sensor" lights on charge

control circuit board (51).

With wires disconnected, check

ohm values of the charge control

resistor (49). Must be 175 ohm

center to top and center to bottom.

Check the charge level selector

switch. Unit should not be in

"HIGH" mode on warm days.

All lights "ON" regardless of

outdoor temperature

Lights work properly

Replace resistor (49).

Check unit wiring and

charge control circuit

board fuses.

Replace charge control

circuit board (51).

Defective

Ok

Defective

Check for 32 VDC between the "C" position

(thermostat connection) on the charge control circuit

board's terminal block and the top low voltage fuse on

the charge control circuit board (51). Check fuse.

Check control

transformer(s) (55) and the

two lower 3AMP fuses.

Replace charge control

circuit board (51).

No voltage present

Ok

Replace charge

control circuit

board (51).

Ok

1. With outdoor air temperature sensor wiring disconnected and the selector
switches on the charge control circuit board set to "WINTER" and "AUTO"
positions, jumper outdoor air sensor terminals "W" and "R". The bottom
Outdoor Temperature Sensor light on charge control circuit board should be
off.

2. Jumper "W", "R", and "B" terminals. The middle and bottom Outdoor
Temperature Sensor lights on charge control circuit board should go off.

Voltage present

Replace charge control

circuit board (51).

Replace outdoor air

temperature sensor(61).

Ok

Defective

Repair

Ok

Check top

(1 AMP) fuse.

Set to auto

position.

Ok

Not

Ok

Defective

Replace fuse

and/or

transformer

(55).

Fuse Ok

Check outdoor

sensor wiring and

replace the fuse.

Fuse bad

Page 4

Check operation of the three

"Outdoor Temperature

Sensor" lights on charge

control circuit board.

With wires disconnected, check

ohm values of the charge control

resistor. Must be 175 ohm center

to top and center to bottom.

Check the charge level selector

switch. Unit should not be in

"HIGH" mode on warm days.

All lights "ON" regardless of

outdoor temperature

Lights work

properly

Replace resistor.

Check unit wiring and

charge control circuit

board fuses.

Ok

Defective

Check for 32 VDC between the "C" position

(thermostat connection) on the charge control circuit

board's terminal block and the top low voltage fuse on

the charge control circuit board.

Check control

transformer(s) and the

two lower 3AMP fuses.

No voltage present

Ok

Ok

1. With outdoor air temperature sensor
wiring disconnected and the selector switches
on the charge control circuit board set to
"WINTER" and "AUTO" positions, jumper
outdoor air sensor terminals "W" and "R". The
bottom Outdoor Temperature Sensor light on
charge control circuit board should be off.

2. Jumper "W", "R", and "B" terminals. The
middle and bottom Outdoor Temperature
Sensor lights on charge control circuit board
should go off.

Replace charge

control circuit

board.

Replace outdoor

air temperature

sensor.

Ok

Defective

Repair

Ok

Check top

(1 AMP) fuse.

Set to auto

position.

Not

Ok

Defective

Replace fuse

and/or

transformer.

Fuse Ok

Check outdoor

sensor wiring for

short to ground and

replace the fuse. If

fuse continues to

open, replace charge

control circuit

board.

Fuse bad

Check VAC on resistor (66) from middle to top

and middle to bottom. Reults vary depending on

number of charging lights on:

1 light on = 24 VAC middle to top and bottom

2 lights on = 0 VAC middle to top; 24 VAC

middle to bottom

3 lights on = 0 VAC middle to top and bottom

Replace charge

control thermostat.

Defective

Voltage present

Ok

Incorrect