Steffes HPB22 Troubleshooting Guide User Manual

Page 7

Advertising
background image

Page 5

Heat Pump Booster

Function: Air Delivery

Problem: Blower does not run

Before starting any of the procedure below, check voltage on load side of all HPB circuit

breakers. Check for 24 VAC between each of the low voltage fuses and the "C" position on the

charge controls circuit board's terminal block. Put heater into peak mode.

Initiate a peak mode.

Check for 24 VAC across "R" and "C"

terminals on booster interface board (21).

Jumper terminal "R" to "W" on

the interface board (21).

Troubleshoot and repair

field wiring.

Voltage present

No voltage

Check for operation

of fan relay (54).

Check field wiring

and wall thermostat.

Motor runs

Motor does not run

Check voltage at

relay coil.

Check supply voltage to

core blower motor (38).

Relay will not operate

Relay closes

Replace interface

board (21).

Replace fan

relay (54).

No voltage

Voltage

present

Check unit wiring and

fan limits (44 & 27).

Replace core

blower motor (38).

Improper

Voltage

Proper

Voltage

Page 6

Initiate a peak mode.

Check for 24 VAC across "R" and "C"

terminals on booster interface board.

Jumper terminal "R" to "W" on

the interface board.

Troubleshoot and repair

field wiring.

Voltage present

No voltage

Check for operation

of fan relay.

Check field wiring

and wall thermostat.

Motor runs

Motor does not run

Check voltage at

relay coil.

Check supply voltage to

core blower motor.

Relay will not operate

Relay closes

Replace interface

board.

Replace fan

relay.

No voltage

Voltage

present

Check unit wiring and

fan limits.

Replace core

blower motor.

Improper

Voltage

Proper

Voltage

Check system

wiring.

Closed

Replace fan limit

switch(es).

Open

Advertising