Steffes HPB22 Troubleshooting Guide User Manual

Page 6

Advertising
background image

Page 4

Heat Pump Booster

Function: Air Delivery

Problem: Cool discharge air

Before starting any of the procedure below, check voltage on load side of all HPB circuit

breakers. Check for 24 VAC between each of the low voltage fuses the "C" position on the

charge control circuit board's terminal block..

Blower delivers cool

discharge air.

Initiate a Stage I heat call.

Make sure the duct sensor (52) is

positioned properly and check field wiring.

With duct sensor (52) disconnected

at interface board (21), jumper the

red and black terminal block

positions. Watch for damper to open.

Ok

Cold Stage One

Does the charging system work

correctly? Refer to the Theory of

Operation in the Appendix of the

Owner's Manual.

Cold All Stages

Disconnect the yellow wire

from the damper motor (22).

Initiate a heat call, check

voltage between the yellow

wire and the red wire.

Refer to the appropriate

core charging sections of

this troubleshooting guide.

No

Yes

Check voltage between

the yellow wire and

the blue wire.

Are the sensors on the duct

sensor (52) and the air

discharge controller (45) open.

24 VAC

0 VAC

Replace the interface

board (21).

Replace the damper

motor (22).

24 VAC

0 VAC

Check unit

wiring.

Replace

appropriate

sensors.

No

Yes

Fix unit

wiring.

Replace the interface

board (21).

Correct

Incorrect

Damper doesn't

open

Replace duct

sensor (52).

Damper opens

Repair

Not Ok

Page 5

Blower delivers cool

discharge air.

Initiate a Stage I heat call.

Make sure the duct sensor is positioned

properly and check field wiring.

With duct sensor disconnected at

interface board, jumper the red and

black terminal block positions. Watch

for damper to open.

Ok

Cold Stage One Only

Does the charging system

work correctly? Refer to
the Theory of Operation.

Cold All Stages

Disconnect the red wire from

the damper motor. Initiate a

heat call, check voltage

between the yellow wire and

the red wire.

Refer to the appropriate core

charging sections:

Unit Undercharges
Unit Overcharges on Warm Days
Unit Will Not Charge (Unit has no
charge) or Control Board Lights
are Off

Check voltage between

the yellow wire and

the blue wire.

COLD ALL STAGES: Are both of the

sensors on the air discharge controller open?

COLD STAGE ONE ONLY: Are both of the

sensors on the duct sensor open?

24 VAC

Replace the

interface board.

Replace the

damper motor.

24 VAC

0 VAC

Check unit

wiring.

Replace air

discharge

controller or
duct sensor.

Yes

Fix unit

wiring.

Replace the interface

board.

Correct

Incorrect

Damper

doesn't

open

Replace duct

sensor.

Damper opens

Repair

Iniate emergency

heat call.

Not Ok

Uncertain

No/Uncertain

Now Warm

Still Cold

0 VAC

No

Yes